IMC Networks iMediaChassis/6 Network Router User Manual


 
5
Wiring Instruction Guidelines for iMediaChassis/20-2DC
1. Connection of a suitable grounding conductor to the grounding terminal
at each power supply module (a minimum 14AWG copper conductor
should be suitable based on a 15A circuit breaker requirement).
2. Connection of suitable supply wiring to the plus and minus terminals at
each power supply module (a minimum 14AWG copper conductors is
considered suitable based on the 11A input maximum). The input
terminal block at the power supply module is suitable for 22-14 AWG
copper wire.
3. A suitable listed circuit breaker shall be provided in the building
installation as the unit's disconnect device. The branch circuit rating (i.e.
minimum 15A listed circuit breaker, etc.).
DC Power Supply Module Wiring Instructions
The following diagram shows the wiring configuration for a -48 VDC power supply
module for the iMediaChassis/20-2DC.
NOTE
The chassis is protected against incorrect wiring configurations. When wired
incorrectly, the chassis will not function, but no damage will occur.