Liebert 6000RT230 Power Supply User Manual


 
1 SLI-23185QS6_Rev0_09-2012
Liebert
®
GXT3
Quick Start Guide 5000-6000VA RT230 Models
The Liebert GXT3 is shipped with the following items:
Terminal Block Communication terminals
Compact disc with:
o Liebert MultiLink®
o Configuration program
o User manual (electronic version)
USB cable, one; 2m (6-1/2 ft.) long
Rack handles with mounting hardware
Plastic tower support base, one set
Plastic Bezel
Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
If the UPS is intended to be installed in the Tower orientation, locate the support base and spacers then assemble the two
stand assemblies with an even number of spacers in each assembly. Insert the UPS between the support base
assemblies with adequate space between the assemblies as shown in the picture below. Note the display should be
located on the upper half of the unit in the Tower orientation. To rotate the display with the bezels removed, depress the
grooved tabs on the sides and rotate it 90 degrees clockwise. If the USP is to be installed in a rack enclosure, follow the
instructions provided with the rack mounting hardware for proper installation.
The UPS is hardwired input with a conduit entry knockouts provided. Input and output wiring should be installed in
separate conduits. All wiring should be done in accordance to all local and national electrical codes. Before wiring the
UPS ensure that the breaker in the external upstream panelboard is OFF.
UPS Model
Recommended
(Maximum) External
Over Current
Protection
Recommended Wire
(All wires)
75 degC Copper Wire
Maximum Wire
Accepted by
Terminal Block
Terminal Block
Torque
GXT3-5000RT230
GXT3-6000RT230
32A
4mm
2
(10 AWG)
6mm
2
(8 AWG)
2.26 Nm (20 in-lb)
Terminal Block Connections
5000-6000 VA models
L
N
L
N
OUTPUT
INPUT
The UPS is equipped with a POD containing output receptacles; connect the equipment to be protected to the output
receptacles.