Liebert 700-2200 VA Power Supply User Manual


 
6
MINI-TOWER INSTALLATION
1. Unpack the UPS carefully noting the packing method. Retain the box and
packing material for possible future shipment.
CAUTION: The UPS is heavy (see specifications). Take proper precautions
when lifting or moving it.
2. Visually inspect the UPS for freight damage. Report damage to the carrier and
your dealer.
3. Locate the UPS indoors where it cannot be accidentally disconnected. Locate
it in an area with unrestricted airflow, away from water, flammable liquids,
gases, corrosives, or conductive contaminants. Maintain a minimum of four (4)
inches (102 mm) clearance around the UPS. Maintain an ambient temperature
range of 32° to 104° F (0° to 40° C).
NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery
life.
4. Ensuring load equipment is turned off, plug all loads into the UPS output
receptacles.
5. Plug the UPS into a dedicated wall receptacle properly protected by a circuit
breaker or fuse in accordance with the National Electric Code (ANSI/NFPA 70)
or local codes. Use a 15 amp rated device for the 700, 1000, or 1400 VA
units, and a 30 amp device for the 2200 VA unit. The wall receptacle must be
grounded.
6. Turn on the UPS, by pressing the On/Off button, then turn on the connected
load equipment. The UPS is ready for normal operation.