Liebert GXT3 Surge Protector User Manual


 
Communication
23 Liebert
®
GXT3
5.2 USB Port Communication
The standard B-type USB port is used to connect the UPS and network server or other computer
system using Liebert MultiLink
®
. The configuration program can be completed through the
communication port.
5.2.1 Configuration Program
Accessing the Configuration Program via USB is a new feature of the Liebert GXT3. For most users,
the factory default settings will be adequate. This section illustrates the features available for
modification, as well as the factory default setting.
The USB configuration program allows these features of the Liebert GXT3 to be changed:
Enable/Disable Auto-Restart
Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass
disabled
Set the Low Battery Warning alarm time from 2 to 30 minutes
Enable/Disable the Auto-Battery test
Enable/Disable Auto-Restart after removing Remote shutdown
Set the wiring mode of Remote shutdown
Set the Auto-Enable output
Set the Auto-Battery test to 7, 14, 21 or 28 days
Select the number of external battery cabinets connected to the UPS to adjust the remaining run
time calculated by Emerson
®
software products
Select one of multiple output voltages to match various voltages (see Table 6).
NOTICE
The output voltage settings cannot be changed while the UPS is On and powering connected
loads.
Table 6 Output voltage option, all models
Factory Default Setting Output Voltage Option
230VAC 220VAC, 230VAC and 240VAC
NOTE
Programming the output voltage of a 230V model of the Liebert GXT3 to 220V automatically
derates the UPS to 96% of both the VA and Watt ratings (refer to 9.0 - Specifications for VA
and Watt ratings).
NOTE
This program is compatible with UPS models beginning with ‘GXT3,’ as in
‘GXT3-3000RT230.’ It is not compatible with earlier versions of the Liebert GXT UPS.
A computer running Windows 2000
®
, XP
®
or Vista
®
is required to set up and run the
configuration program.