Liebert GXT96VLRT2UL Power Supply User Manual


 
7
LRT
TM
Battery Cabinet Specifications
Model Number GXT96VLRT2UL
Compatible With
UPStation GXT:
1800RT-208, 2000RT-120, 2000RT-230, 2700RT-208,
3000RT-120 and 3000RT-230 VA UPS’
DIMENSIONS: in. (mm)
Unit W x D x H 15 x 27 x 29 (381 x 686 x 737)
WEIGHT: lbs (kg)
Unit 600 lbs (272kg)
INPUT AC PARAMETERS
Voltage Range 85 to 265VAC
Frequency >40 to <70 Hz; auto sensing
Input Power Factor >0.95
Current Reflected THD 30% THD maximum
Current Rating < 4A at 120VAC, < 2A at 230VAC
Input Power Connection IEC320-C14 recessed plug, with input cords:
(1) 6’ cord with NEMA 5-15P
Fuse Rating 6.3 A
OUTPUT DC PARAMETERS
Output Sockets (2) per LRT cabinet
Interconnect Cable (1) 9.8’ (3m) cable with appropriately keyed plugs
Protection (1) resettable DC circuit breaker
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x
Rating
8 x 12V x 65.0Ah
Approved Battery
Manufacturers:
CSB, Panasonic, and Yuasa
Recharge Time <20 Hours to 95% capacity after full discharge into 100% load
ENVIRONMENTAL
Operating Temperature +32° F to + 104° F (0° C to +40° C) for altitudes
0 to 5,000 ft (1,500m);
+32° F to + 95° F (0° C to +35° C) for altitudes
5,000 ft (1,500m) to 10,000 ft (3,000m)
Storage Temperature +5° F to + 122° F (-15° C to +50° C)
Relative Humidity 0% to 95%, non-condensing
Audible Noise < 45 dBA, at 1 meter
AGENCY
Safety UL 1778; c-UL Listed; EN 50091-1; CE low voltage directive
Surge IEEE 587 Category A; EN61000-4-5,
Level 3 (L-E), Level 2 (L-L)
ESD EN6100-4-2, Level 3
Susceptibility EN6100-4-3, Level 2
Electrical Fast
Transient/Burst
EN6100-4-4, Level 3
Immunity EN50082-1
EMI/EMC FCC Part15, Class A; EN50081-1; EN 55022, Class B;
CE EMC Directive
Additional information on this product can be located on our web site
(www.liebert.com
) or FastBak server (614) 841-5471.
DISCONTINUED
PRODUCT