Specifications
26
12.0 SPECIFICATIONS
Table 3 UPS specifications
Model Number
PS1000RT2-230 PS1440RT2-230
PS2200RT2-230
PS2200RT2-230E
PS3000RT2-230
PS3000RT2-230E
Power Rating, VA/W 1000VA/750W 1440VA/1080W 2200VA/1650W 3000VA/2250W
Dimensions, W x D x H, mm (in)
Unit
87 x 557 x 430
(3.43 x 22 x 17)
87 x 557 x 430
(3.43 x 22 x 17)
87 x 612 x 430
(3.43 x 24.1 x 17)
87 x 612 x 430
(3.43 x 24.1 x 17)
Shipping
300 x 706 x 598
(11.8 x 27.8 x 23.5)
300 x 706 x 598
(11.8 x 27.8 x 23.5)
333 x 864 x 598
(13.1 x 34 x 23.5)
333 x 864 x 598
(13.1 x 34 x 23.5)
Weight, kg (lbs)
Unit 28 (61.7) 31.0 (68.2) 35.0 (77.0) 37.0 (81.6)
Shipping 36.6 (80.7) 39.0 (85.8) 43.6 (95.9) 45.6 (100.5)
Input AC Parameters
Rated Input Voltage 220/230/240VAC
Surge Protection 660J
Voltage Range Without
Battery Operation
158VAC - 283VAC, configurable
Frequency Range 45 - 65 Hz (±0.1 Hz)
Input AC Inlet IEC-320-C14 IEC-320-C14 IEC-320-C20 IEC-320-C20
Output AC Parameters
Output Receptacles (8) IEC-320-C13 (8) IEC-320-C13
(8) IEC-320-C13
(1) IEC-320-C19
(8) IEC-320-C13
(1) IEC-320-C19
Voltage (Normal mode) 220/230/240VAC (configurable) ±10%
Voltage (Battery Mode)
220/230/240VAC (configurable);
±5% before low battery warning; ±8% after low battery warning
Transfer Time 4-6 ms typical
Waveform Sinewave
Frequency (Normal Mode) 45 - 65 Hz (±0.1 Hz)
Frequency (Battery Mode) 50 or 60 Hz (±0.5 Hz); auto sensing
Overload Warning >100 - 110%
Overload Shutdown >200% - short circuit; after 15 cycles (normal mode)
Battery Parameters
Type Valve-regulated, nonspillable, lead acid
QuantityxVoltagexRating 4 x 12V x 7Ah 4 x 12V x 7Ah 6 x 12V x 7Ah 6 x 12V x 9Ah
Battery Manufacturers CSB, B&B Battery, and EnerSys
Backup Time See Table 5 - Battery run times
Full Load 11 5 5 6
Half Load 26 16 16 16
Recharge Time 4 hours to 90% of rated capacity, after full discharge into resistive load
Environmental
Operating Temperature 0°C to + 40°C (+32°F to + 104°F)
Storage Temperature -15°C to + 40°C (+5°F to + 104°F)
Relative Humidity 0% to 95%, non-condensing
Operating Altitude
Up to 2,000m (6,500 ft) at 35°C (95°F)
without derating
Up to 3,000m (10,000 ft) at 35°C (95°F)
without derating
Audible Noise
<40 dBA, internal fan(s) Off
<50 dBA, internal fan(s) On
<40 dBA, internal fan(s) Off
<60 dBA, internal fan(s) On