Appendix A - Series 600 UPS Site Planning Data 87
Table 6 338-500 kVA Multi-Module Unit, 208 Volt - Standard Module
UPS
Rating
* Rectifier
AC
Input
Current
Inverter
AC
Output
Current
Required
Battery
Discon-
nect
Rating
Maximum
Battery
Current
at End of
Discharge
%
Efficiency
at
Full Load
Maximum
Heat Dis-
sipation
BTU/hr.
Dimen-
sions
Inches
Approx.
Weight
Lb.
Floor
Loading
Lb./
Sq.Ft.
kVA kW Nom Max Nom Max Amperes Amperes
Full
Load (WxDxH)
(Un-
packed)
(Distribu-
ted
Loading)
338 270 980 1226 937 1171 1000 998 92 91138 128x38x78 8600 255
400 320 1170 1462 1110 1388 1200 1176 92 101457 218x38x78 10250 214
400 360 1300 1625 1110 1388 1200 1323 92 114140 218x38x78 10250 214
500 400 1462 1827 1388 1735 1600 1470 92 126822 218x38x78 10950 228
500 450 1625 2031 1388 1735 1600 1654 92 142675 218x38x78 10950 228
Applicable
Notes:
1,4,5,7,8,
9,11,12
2,5,7,8,
9,11,12
66,8,9,
11,12
——1313—
For explanation of notes, see referenced numbers in
10.1 - Notes
* Nominal Input Power Factor 0.85 lagging at full load; 9% Maximum Total Input Harmonic Current Distortion (THD) at full load.
Table 7 338-500 kVA Multi-Module Unit, 208 Volt - Standard Module With Optional Low
Distortion Input Filter
UPS
Rating
* Rectifier
AC
Input
Current
Inverter
AC
Output
Current
Required
Battery
Discon-
nect
Rating
Maximum
Battery
Current
at End of
Discharge
%
Efficiency
at
Full Load
Maximum
Heat Dis-
sipation
BTU/hr.
Dimen-
sions
Inches
Approx.
Weight
Lb.
Floor
Loading
Lb./
Sq.Ft.
kVA kW Nom Max Nom Max Amperes Amperes
Full
Load
(WxDxH)
(Un-
packed)
(Distribu-
ted
Loading)
338 270 895 1119 937 1171 1000 998 92 91138 128x38x78 9100 270
400 320 1055 1319 1110 1388 1200 1176 92 101457 218x38x78 10750 224
400 360 1187 1484 1110 1388 1200 1323 92 114140 218x38x78 10750 224
500 400 1333 1667 1388 1735 1600 1470 92 126822 218x38x78 11650 243
500 450 1500 1875 1388 1735 1600 1654 92 142675 218x38x78 11650 243
Applicable
Notes:
1,4,5,7,8,
9,11,12
2,5,7,8,
9,11,12
66,8,9,
11,12
——1313—
For explanation of notes, see referenced numbers in
10.1 - Notes
* Nominal Input Power Factor 0.92 lagging at full load; 4% Maximum Total Input Harmonic Current Distortion (THD) at full load.