Liebert Interceptor II Surge Protector User Manual


 
Surge Suppression Systems
Installation, Operation and Maintenance Manual 9 Liebert TVSS Units SL-22085 Rev 2, 11/2006
7. An external circuit breaker is not necessary for over-current protection for most units (LPL Units require a 30A or less circuit
breaker). However, it is recommended that the SPD be connected in series with a circuit breaker denoted in the tables below
(also indicated on the “Dimensional Information” pages in this manual). The SPD shall be connected in accordance with all
national and local electrical codes.
5. Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground)
marked G, of the SPD using the wire range listed below. To yield the best performance of the SPD within the electrical
distribution system, keep all conductors as short as possible and avoid sharp bends.
If the SPD model is a Wye confi gured unit (4W+G),
and a Neutral connection is not available, please contact factory.
Surge Voltage Ratings. To obtain the suppression voltage ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated,
in accordance with the Standard for Safety, Transient Voltage Surge Suppressors (TVSS), Standard 1449, Second Edition, dated August
15, 1996, marked on this product, the suggested wire size must be utilized to connect the unit to your facilities power grid.
Connections made with conductors other than the size provided may result in different SVRs.
6. Connection to Form ‘C’ contacts shall be with #18 – 22 AWG. The ratings of the Form ‘C’ contacts are 5 amps at 250 VAC
maximum with a power factor of 1.0. For additional information on Interceptor II connections, see page 15.
7. Apply power. The surge protector is fully operational when the GREEN LEDs on the modules and the front door of enclosure are
illuminated. If the GREEN LEDs are extinguished or a RED LED is illuminated, check to ensure that power is applied to the SPD.
If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge Protection
at 1-800-288-6169 or 1-607-724-2484.
8. Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished or the RED LED is
illuminated. Please contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.
9. The protection modules in these SPDs may be replaceable, contact Liebert/Emerson Network Power Surge Protection for
replacement. (Note: ACV, LPM, & LPL units do not have replaceable modules).
TVSS
Series
Model #
Allowable Range Factory Suggested Size
Circuit Breaker Size
Connection Wire Size
Circuit Breaker
Size
Connection
Wire Size
With Disconnect Without Disconnect With Disconnect Without Disconnect
Interceptor II
Hybrid Advantage
Type SS Series
LM Series
AccuVar
PowerSure LPM
SI016 – SI025
SI032 – SI050
SI060 – SI075
SI100
Hxxxxx111 (250kA)
Hxxxxx222 (320kA)
Hxxxxx333 (400kA)
Hxxxxx444 (750kA)
All Units
LM060 – LM080
LM100 – LM150
LM200 – LM250
All Units
LPM 100-2
LPM 160
N/A
15A – 150A
15A – 175 A
15A – 175A
15A – 175A
15A – 150A
15A – 175A
15A – 175A
15A – 175A
N/A
15A – 150A
15A – 175A
15A – 175A
N/A
N/A
N/A
15A – 175A
15A – 175A
15A – 175A
15A – 100A
15A – 30A
30 Amp
30 Amp or less 30 Amp Required
#14 – 1/O
#14 – 2/O
#14 – 2/O
#14 – 2/O
#14 – 1/O
#14 – 2/O
#14 – 2/O
#14 – 2/O
N/A
#14 – 1/O
#14 – 2/O
#14 – 2/O
N/A
N/A
N/A
#14 – 2/O
#14 – 2/O
#14 – 2/O
#14 – #2
#14 – #10
60 Amp
80 Amp
80 Amp
100 Amp
60 Amp
80 Amp
80 Amp
80 Amp
80 Amp
40 Amp
40 Amp
100 Amp
30 Amp
30 Amp
#6
#4
#4
#2
#6
#4
#4
#4
#4
#8
#8
#2
#10
#12 Provided
#12 Provided
PowerSure LPL
N/A
N/A
.31 (4X)
0.500
4.000
8.750
8.000
0.375
3.500
Service Panel
for Loads to
be Protected
Phase L3/C
Phase L2/B
Phase L1/A
Disconnect/Main
Breaker for Panel
Neutral Buss
Ground Buss
Dedicated
Disconnect
(Optional)
Installation, Operation and Maintenance Manual 20 Liebert TVSS Units SL-22085 Rev 2, 11/2006
Surge Suppression Systems
PowerSure Medium Exposure Series — Type LPM 100-2
0.375
6.750
0.500
2.000
6.000
Phase A Phase B Phase C
Service
.31
(4X)
3.000
4.000
Phase A Phase B Phase C
Service
Service Panel
for Loads to
be Protected
Phase L1/A
Phase L2/B
Phase L3/C
Disconnect/Main
Breaker for
Panel
Neutral Buss
Ground Buss
Dedicated
Disconnect
(Optional)
Unit is supplied from the
factory with a minimum
length of 18” of #12
wire for connection. It
is recommended that a
30A circuit breaker be
used for installation.
Unit is equipped with Summary
Alarm Contacts. The #18 wires
are designated as follows:
YELLOW = Normally Open
ORANGE = COMMON
BLUE = Normally Closed
PowerSure Medium Exposure Series — Type LPM 160
Unit is supplied from
the factory with a
minimum length
of 18” of #10 wire
for connection. It is
recommended that a
30A circuit breaker be
used for installation.
Liebert Interceptor II Printer S11 11 12/29/06 1:37:58 PM