Electrical (continued from page 1)
• Automatic, battery protecting low voltage disconnect (LVD)
• Advanced battery diagnostics and management system
• Temperature compensated battery charger
• 24 hour recharge time
• High frequency, very low ripple current charger
• Input and output disconnect switch
• Battery disconnect switch
NOTES:
1) Continuous Duty
2) Total Load Not to Exceed System Rating
System Input/Output Ratings
Warranty
Standard Warranty
Lightolier will provide parts and on-site labor for the first 90 days following
shipment of product, and parts only for an additional 270 days.
Extended Warranty
(Available with purchase of Factory Start-Up Service) Lightolier will provide
parts and on-site labor for the first 12 months following start-up of the
product, and parts only for an additional 12 months.
System One-Line Diagram
Pin Description Function
8 Normal System Functioning Normally
6 Load On Reserve Double Conversion Inverter Not Operating
9 Power Failure Load Supplied by Battery
7 End of Discharge Period Unit Will Soon Stop Operating
5 Common Common Connection to Above 4 Signals
Computer Interface Pin Configuration
(AS/400™)
Listed to
UL 924
SYSTEM INPUT INPUT AVAILABLE OUTPUT VOLTAGES/ OCB POLE SPACES
RATING VOLTAGE AMPS
1
MAX. LOAD AMPS
2
AVAILABLE
120 V 208 V 240 V 277 V
14,000 VA 277 63.2 116.5 — — 50.5 12
208/240 80.8/70.0 116.5 67.3 58.3 — 12
L1PH Series Uninterruptible Power Supplies
L1PH
Page 2 of 2 14.0 kVA Single Phase UPS System
Lightolier
a Genlyte Thomas Company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504
Battery
Maintenance free, sealed lead calcium battery has an estimated service life of
10 years, and an operating temperature range of 65°F (19°C) to 85°F (30°C).
Options
0 = None
1 = PC Format Diagnostics Software
4 = Remote Display + “5”
5 = Additional RS-232
Job Information Type: