Lindy 20703 Computer Accessories User Manual


 
English Manual
Module Cover
Terminals
2-Port-PCB
Chassis
Shielding Contact
Strain Relief
Ground Connector
LINDY GigapatchPanel
The LINDY GigaPatchPanel is supplied with 16 or 24 Cat 6 ports. The new modular construction allows you to
install the panels with any even number of ports between 2 and 24, partially equipped panels can be extended or
completed with the addition of dual modules at any time. This means that the valuable space inside your rack can
be fully optimised, for the future expansion of your network.
The newly developed LSA-rct technology allows a fast and reliable connection of the wires to the terminals. Each
unit is supplied with a suitable crimping tool, however there is also a premium tool available which allows you to
connect 4 wires simultaneously and thus helps to increase efficiency and lower the costs of the network installation.
? Up to 12 shielded dual RJ45 Cat 6 modules per unit
? PCB-terminals optimised for fast data transfer
? Strain relief’s are attached - so they won’t get lost
? Additional strain relief by use of a cable tie is possible
? Coding scheme both, EIA/TIA 568 A and B
? Crimping tool supplied
? Connection via LSA-rct terminals
? Cores with 22-24 AWG can
be accommodated
? Pairs can be lead
directly to the terminals
no need to untwist
them
Preparation of the cable
Foil- or Braid shielded cable
Cut away the outer sheath by approx 65mm with a
cable or sharp knife. Make sure to cut only as deep as
the shielding allows, don’t damage the insulation of the
wires!
Cut the foil or the braid shielding as shown in the
picture so that you leave approx 10mm of the shielding.
Wind the shielding wire around the 10mm left of the
shielding, it will be clamped later beneath the strain
relief.
If present, shorten the shielding foil of the single pairs
(Pimf-cable only) to the same length. Untwist the pairs
for 13mm at most and connect the wires using the
following colour scheme
untwist 13 mm at most
NEXT Pairs 1,2 – 3,6
NEXT
Pairs 3,6
4,5