Micro Technic PV-5127 Power Supply User Manual


 
Users Manual & Installation Guide
PV- 5127: Power supply module with UPS
Page 31 of 31
Differences between PV-5127 and PV-5127A
The PV-5127 is available in a version without UPS and battery charger. The ordering code for this
product is PV-5127A. These things are different in this version:
The mains voltage range is nominally 10-35V instead of 18-35V. The mains monitor
reports mains failure at mains voltage below 9.0V and mains OK at above 9.5V, instead of
16.5V and 17.5V, respectively.
The battery charger is omitted.
The input selector circuit is omitted.
J1 for battery temperature sensor is omitted.
CN3 for “RS232” UPS communication is omitted.
Block diagram of the PV-5127A