PV- 5127: Power supply module with UPS
Page 21 of 31
mounted directly on the battery. The charging is disabled when the temperature according to this
sensor rises above 55°C, and enabled when it falls below 45°C. The J1 input has the following
function:
Installed on J1 Charger function
Nothing Disabled. See note.
A jumper Enabled (factory default)
A KTY11-5 sensor Enabled when not too hot
Note: When using the PV-5127 with a PV-1075 NiMH battery module, you must disable the PV-
5127 charger by leaving J1 unconnected.
You can connect a Battery LED to the CN2 connector. The LED shows these statuses:
Battery LED Meaning
Off
Battery voltage OK (medium or full). If mains is present and the charger is enabled,
the charger is in trickle charge mode, otherwise it is off.
Flashing
Charger is in fast charge mode.
Steady on
Battery error. This indicates that the battery is either empty, low, or disconnected.