Minuteman UPS MM-AVR Power Supply User Manual


 
7
SPECIFICATIONS
Model MM-AVR 600 MM-AVR 800 MM-AVR 1200
Capacity 600VA/300W 800VA/480W 1200VA/600W
Phase Single phase
Voltage Range 95V-145V ±3V
Input
Frequency 60HZ ±5HZ
Voltage
(battery mode)
120V ±10%
Waveform
AC mode - follow utility
Battery mode - Step Sine Wave
Frequency AC mode - follow utility, Battery mode - 60Hz ±5Hz
Frequency <0.5HZ (battery operation)
Output
Transfer Time Typical 4ms, max 10ms
Surge Protection 320 Joules
Input Protection Compliance with IEEE 587
Protection
Short Circuit Fuse
Type 12V Sealed non-spillable lead acid, maintenance free
Recharge After full discharge, 8 hours to 90% capacity
Backup Time
(full load)
3 min
Charge Current 350mA~1A
Battery
Battery
Configuration
1x12V/7AH 1x12V/9AH 2x12V/7AH
AC Mode
Green and Orange LED on, Red LED off,
No Alarm
Charging Battery Orange LED on
Battery Mode
Green and Orange LED off, Red LED flash,
Alarm slow beep
Indication
Battery Low
Green and Orange LED off, Red LED flash,
Alarm fast beep
Audible Noise
at 1 m (3 ft)
<45dB
Temperature
0 to 40
°
C (+32 to +104
°
F)
Environment
Humidity 0% - 90% Non- Condensing