Mitsubishi Electronics A1SJ71E71N-B2 Network Card User Manual


 
3
[Function]
(1) Data communication function (TCP/IP Communication and UDP/IP Communication)
Communication Function Description QnA series A series
Using read/write data in the PLC CPU Reads/writes PLC CPU data from/to an external device.
!
!
Procedure exist Using fixed
buffers
No Procedure
Reads/writes any data between PLC CPU and an external device
using fixed buffer of the Ethernet modules.
! !
Using random access buffers
Exchanges data with multiple external devices, using the Ethernet
random access buffers. (no need to specify external device)
! !
Using data link instructions
Reads/writes PLC CPU data of other stations via the Ethernet
using data link instructions.
! N/A
File transfer (FTP Server Function)
Reads/writes files in the local station using the FTP server
function, from an external device.
! N/A
(2) Other functions
Function Description QnA series A series
MELSECNET/10 relay communication
Data communication is enabled over a network system where
Ethernet and MELSECNET/10 or multiple Ethernet networks are
present.
!
N/A
Router relay communication (Router
relay function)
Communicates data via routers and gateways. (Ethernet module
does not function as a router.)
!
!
External device existence confirmation
Checks whether or not the external device operates normally after
communication has been established (open processing).
! !
Paring open communication
Receiving connection and transmitting connection are opened as a
single pair. (For fixed buffer communication.)
! !
Communication using automatic open
UDP port
Communication is enabled automatically after initial processing is
completed of local station Ethernet module. (Opening and closing
by a sequence program is unnecessary.)
!
N/A
Simultaneous broadcast
Data is broadcasted simultaneously to all stations on the same
Ethernet network where the Ethernet module is located. (Using
UDP/IP)
! !
Access PLC CPU from GX Developer using Ethernet connection.
! !
Please refer to the new module's User's Manual for the function versions and serial numbers of the products !: Applicable
(CPU module and GX Developer) related to the above functions.
[Performance Specifications]
Specification
AJ71QE71N-B5T
A1SJ71QE71N-B5T
AJ71QE71N-B2
A1SJ71QE71N-B2
AJ71E71N-B5T
A1SJ71E71N-B5T
AJ71E71N-B2
A1SJ71E71N-B2
Item
10BASE5 10BASE-T 10BASE2 10BASE5 10BASE-T 10BASE2
Transmission speed 10Mbps
Transmission method Base band
Maximum node-to-node
distance
2500m
(8203ft.)
- 925m (3035ft.)
2500m
(8203ft.)
- 925m (3035ft.)
Maximum segment
length
500m
(1641ft.)
100m
(323ft.) (*1)
185m (607ft.)
500m
(1641ft.)
100m
(323ft.) (*1)
185m (607ft.)
Maximum number of
nodes per connection
100 units/
segment
Cascade
connection,
maximum 4
30 units/ segment
100 units/
segment
Cascade
connection,
maximum 4
30 units/
segment
Transmission
Specifications
Minimum node interval 2.5m (8.2ft.) - 0.5m (1.6ft.) 2.5m (8.2ft.) - 0.5m (1.6ft.)
Number of
simultaneously open
connections allowed
8 connections (Connections usable by the sequence program)
Fixed buffer
1k words × 8 1k words × 8
Send/receive
data storage
memory
Random access buffer
6k words × 1 3k words × 2
Number of occupied I/O points 32 points
5VDC current consumption
AJ71QE71N-B5T :0.48A
AJ71QE71N-B2 :0.56A
A1SJ71QE71N-B5T:0.42A
A1SJ71QE71N-B2 :0.64A
AJ71E71N-B5T :0.48A
AJ71E71N-B2 :0.56A
A1SJ71E71N-B5T:0.42A
A1SJ71E71N-B2 :0.64A
12VDC external supply power capacity
(for transceiver)
(*2) (*2)
*1 Between hub and node.
*2 It is necessary to use a power supply that meets the specifications of the transceiver and AUI cable, considering the voltage drop
(maximum 0.80V) in the module.