Murphy AS710S Switch User Manual


 
Programmable functions
The Autostart 710 has over 30 programmable functions:-
Timers:-
Start delay; preheat, crank and crank cool (dwell) times;
alarm override time; warm-up delay, mains restore delay;
engine cool (run on, off load) time, speed signal delay.
Inputs:-
Inputs 1 and 2 are dedicated for use with low oil pressure
and high engine temperature sensors, switch or analogue
type. Inputs 3, 4 and 5 may be programmed for a range of
uses, including shutdown or warning faults, manual restore
(of mains), test off load, alarm mute, etc. The inputs can be
set up to work with remote contacts which either open or
close when active, with wiring to either +ve or –ve DC.
Outputs:-
6 programmable outputs, each of which may be set
to give one of over 30 signalling or control ‘actions’,
including: Preheat (4 types), Energised to Stop Fuel,
Louvre Control, Generator Available, Common Alarm,
Alarm (muteable), Shutdown Fault, Warning Fault,
Overspeed, Start Fail, individual faults (1 - 5), etc.
Other System parameters:-
Crank release (by engine RPM, generator Hz. or charge
alternator WL voltage), underspeed and overspeed trip
levels (Hz. or RPM); maximum number of start attempts;
high and low battery voltage warning levels; enable or
disable loading of generator in manual mode.
When ordering, please specify:-
AS710S
Generator AC voltage:-
Switch option:-
K = keyswitch
R = rotary (knob) switch
D = 230 VAC
C = 110 VAC
Accessories:-
AS7PROG Hand held programmer key-pad
AS7CA 9 way (interface) to 9 way (PC) comms lead
AS7CB 9 way (interface) to 25 way (PC) comms lead
AS7CC RS232 communications local interface
AS7CD RS232 communications modem interface
AS7CK AS7xx communication and programming software
Rear Facia & Electrical Connection
–ve DC supply
Charge fail input
+ ve DC power supply
+ ve DC (relays)/Emerg. stop
Magnetic pickup input
Output 1
Output 2
A800 enable output
Output 3: – ve, < 250mA
Output 4: – ve DC, 5 A max.
Remote start/mains fail input
Off output: – ve, < 250mA
Manual output
Auto output
5 – 40 VDC
+ ve DC
250mA max.
– ve DC
250 mA max
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
- No connection -
Input 1: low oil pressure
Input 2: high engine temp.
Input 3: programmable
Input 4: programmable
Input 5: programmable
Fuel output
Starter output
Output 5 (alarm): + ve, < 5A
NO
CO
Live
Neutral
+ve DC
16 A max.
Output 6 (gen. contctr)
volt free, 5 A max.
Man. Start
Man. Stop
Generator AC
300 VAC max.
– ve
Index Pin21
16
17
18
19
20
22
23
24
25
26
27
28
29
30
Communications Port
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
22
23
24
25
26
27
28
29
30
21
Typical Connection
manual
start
manual
stop
LOP
HET
IP3
IP4
IP5
RPO3
MCR
Reset
WL
+
Fuse
+ve DC
–ve DC
RPO2RPO4
Magnetic
Pickup
RPO1
MCR1
5A
Emerg.
stop
GCR1
GCR
MCCB
16
17
18
19
20
22
23
24
25
26
27
28
29
30
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
AUTOSTART
710
AutoManual
RAL
RST
RFL
1A
inputs
Fuel
Starter
Alarm
L1
L2
L3
N
L1
L2
L3
N
G
E
N
E
R
A
T
O
R
M
A
I
N
S
UVR500
L1
1 2 3 4 5 6
L2 L3 N
mains
contactor L1L2
L O A D
L3 N
gen.
contactor
Since 1939
Frank W. Murphy Manufacturer
PO Box 470248, Tulsa, Oklahoma 74147, USA
Tel: + 1 918 627 3550 Fax: + 1 918 664 6146
email: sales@fwmurphy.com
web: http://www.fwmurphy.com
Frank W. Murphy Southern Division
PO Box 1819, Rosenberg, Texas 77471, USA
Tel: + 1 281 342 0297 Fax: + 1 281 341 6006
email: sales@fwmurphy.com
Frank W. Murphy Ltd.
Incorporating Modex Automation
Church Road, Laverstock, Salisbury U.K.
Tel: + 44 1722 410055 Fax + 44 1722 410088
Pour service en Français, tél: + 44 1722 410697
email: sales@fwmurphy.co.uk
web: http://www.fwmurphy.co.uk
Macquarrie Corporation
1620 Hume Highway, Campbellfield, Vic. 3061 Australia
Tel: + 61 3 9358 5555 Fax: + 61 3 9358 5558
email: murphy@macquarrie.com.au
Murphy Switch of California
41343 12th Street West, Palmdale, CA 93551, USA
Tel: + 1 661 272 4700 Fax: + 1 661 947 7570
email: sales@murphyswitch.com
web: http://www.murphyswitch.com
Murphy de Mexico S.A. de C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
San Luis Potosí, S.L.P. México 78384
Tel: + 52 48 206264 Fax: + 52 48 206336
email: murmexsl@sanluis.podernet.com.mx
Frank W. Murphy Pte, Ltd.
No. 2 Tuas South Street 2, Sprintecs Building
02-01/02, Singapore 637895
Tel: + 65 863 1398 Fax: + 65 863 0208
email: fwmsales@fwmurphy.com.sg
Frank W. Murphy Ltd. en France
Tel: +33 (1) 30 76 26 26 Fax: +33 (1) 30 76 39 89
Direct usine Tel: + 44 1722 410697
email: sales@fwmurphy.co.uk