Murphy TDX6 Switch User Manual


 
TDX-9106B page 2 of 2
POWER INPUT
INPUT
JUMPER
LCDT,
MARK II,
S1400,
TATTLETALE etc.
TC 1
TC 2
TC 3
TC 4
TC 5
TC 6
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
+
-
+
+
-
+
-
TC 1
TC 2
TC 3
TC 4
TC 5
TC 6
TP 1
COM
TP 2
TP 3
COM
TP 4
TP 5
COM
TP 6
COM
PWR
INPUT
1
2
3
NOTES:
1
Remove input jumper when the thermocouple is
connected to input.
Thermocouple Input
Power input 120 VAC, 80-250 VDC, CD ignition or 24 VDC,
positive or negative ground.
2
3
®
TDX6
Interfaced components must meet area
classification requirements.
4
When using the TDX6 with inductive loads, we recommend
installing a suppression diode across all coils.
5
5
+
Load
4
How to Order
To order the TDX6 use the part number designation diagram below.
Display
F = Fahrenheit
C = Celsius
Models
TDX6 = Square hole mounting
TDXF6 = Round hole mounting
Power Supply/Output
A = CD ignition, 80-250 VDC Positive or Negative Ground or
120 VAC 50-60 Hz Inputs—S.C.R. Outputs.
B = CD ignition, 80-250 VDC Positive or Negative Ground
or 120 VAC 50-60 Hz Inputs—F.E.T. Pulsed Outputs.
††
C = 24 VDC Inputs—S.C.R. Outputs.
D = 24 VDC Inputs—F.E.T. Pulsed Outputs.
††
For use with electromechanical TATTLETALE
®
annunciators.
††
For use with SELECTRONIC
®
or similar solid-state annunciators.
Thermocouple Type
J = Type J
K = Type K
3-1/2 in.
(89 mm)
3-3/4 in.
(95 mm)
3-3/4 in.
(95 mm)
6-3/4 in.
(171 mm)
clearance for plug
4-5/8 in.
(117 mm)
Back View
Side View
4-3/8 in.
(111 mm)
3-9/16 in.
(90 mm)
3-9/16 in.
(90 mm)
Mounting Clamp
Mounting Hole
4-3/4 in. (121 mm)
diameter
120
120
120
1/4 in. (6 mm) dia.
holes (3 places)
Square Hole Mounting
Round Hole Mounting (TDXF6)
Dimensions Typical Wiring Diagram
TDX6 Interface Capabilities
Model
Power Source Rating
LCDT CD Ign., 120 VAC, 12/24 VDC Cl.I, Div.1, Gr.D, Haz. areas*
S1501 120 VAC or 12/24 VDC Cl.I, Div.1, Gr.D, Haz. areas*
MARK II CD Ignition, pos. or neg. grnd Cl.I, Div.2, Gr.D, Haz. areas*
TATTLETALE
®
CD Ign., 120 VAC, 12/24 VDC Non-Hazardous areas
PLC’s, various non-Murphy annunciators–contact factory.
*Note: An isolation barrier is needed between the TDX6 and an Annunciator rated
for Class I, Division 1, Group D, Hazardous Areas.
**Note: When used with approved ignition. Contact Murphy for details.
Shipping Weight: 2 lb. (0.91 kg).
Shipping Dimensions: 5-1/2 x 9 x 6 in. (140 x 229 x 152 mm).
TDX6
– A – F – J
Warranty
A limited warranty on materials and workmanship is given with this FW
Murphy product. A copy of the warranty may be viewed or printed by going to
www.fwmurphy.com/support/warranty.htm
CONTROL SYSTEMS & SERVICES DIVISION
P.O. Box 1819; Rosenberg, Texas 77471; USA
+1 281 633 4500 fax+1 281 633 4588
e-mail sales@fwmurphy.com
MURPHY DE MEXICO, S.A. DE C.V.
Blvd. Antonio Rocha Cordero 300, Fracción del Aguaje
San Luis Potosí, S.L.P.; México 78384
+52 444 8206264 fax +52 444 8206336
Villahermosa Office +52 993 3162117
e-mail ventas@murphymex.com.mx
www.murphymex.com.mx
FRANK W. MURPHY, LTD.
Church Rd.; Laverstock, Salisbury SP1 1QZ; U.K.
+44 1722 410055 fax +44 1722 410088
e-mail sales@fwmurphy.co.uk
www.fwmurphy.co.uk
MURPHY SWITCH OF CALIFORNIA
41343 12th Street West
Palmdale, California 93551-1442; USA
+1 661 272 4700 fax+1 661 947 7570
e-mail sales@murphyswitch.com
www.murphyswitch.com
In order to consistently bring you the highest quality, full featured products, we reserve the right to change our specifications and designs at any time.
MACQUARRIE CORPORATION
1620 Hume Highway
Campbellfield, Vic 3061; Australia
+61 3 9358 5555 fax +61 3 9358 5558
e-mail murphy@macquarrie.com.au
FW Murphy
P.O. Box 470248
Tulsa, Oklahoma 74147 USA
+1 918 317 4100
fax +1 918 317 4266
e-mail sales@fwmurphy.com
www.fwmurphy.com
R
E
G
I
S
T
E
R
E
D
USA–ISO 9001:2000 FM 28221
UK–ISO 9001:2000 FM 29422
Printed in U.S.A. 0591127