National Instruments CFP-2220 Network Card User Manual


 
© National Instruments Corporation 35 cFP-2200/2210/2220
Environmental
The cFP-22xx is intended for indoor use only, but it may be used outdoors
if mounted in a suitably rated enclosure.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2)...........–40 to 70 °C
Note To meet this operating temperature range, follow the guidelines in the installation
instructions for your Compact FieldPoint system.
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2)...........–55 to 85 °C
Ingress protection................................... IP 20
Operating humidity
(IEC 60068-2-56)...................................10 to 90% RH, noncondensing
Storage humidity
(IEC 60068-2-56)...................................5 to 95% RH, noncondensing
Maximum altitude..................................2,000 m
Pollution Degree (IEC 60664) ...............2
Shock and Vibration
To meet these specifications, you must panel mount the Compact
FieldPoint system and affix ferrules to the ends of the power terminal wires.
Operating shock
(IEC 60068-2-27)...................................30 g, 11 ms half sine;
50 g, 3 ms half sine;
18 shocks at 6 orientations
Operating vibration,
random (IEC 60068-2-64)...................... 5 g
rms
, 10 to 500 Hz
Operating vibration,
sinusoidal (IEC 60068-2-6)....................5 g, 10 to 500 Hz
Special Conditions for Marine Applications
Some products are Lloyd’s Register (LR) Type Approved for marine
applications. To verify Lloyd’s Register certification, visit
ni.com/
certification
and search for the LR certificate, or look for the Lloyd’s
Register mark on the product.