Appendix C Fieldbus Parameters
FieldPoint FP-3000 User Manual C-12
©
National Instruments Corporation
LIM_NOTIFY
A limit on the number of unconfirmed alarm/event notification messages
the device can have active at once. This must be less than or equal to
MAX_NOTIFY.
LO_ALM
The current state of the low alarm, along with a time and date stamp.
LO_LIM
The limit, in PV units, beyond which the low limit alarm is considered
active.
LO_LO_ALM
The current state of the low-low alarm, along with a time and date stamp.
LO_LO_LIM
The limit, in PV units, beyond which the low-low limit alarm is considered
active.
LO_LO_PRI
The priority of the low-low limit alarm.
Table C-8.
Linearization Types
Type Description
Direct The block output is directly taken from the transducer value:
Indirect The block output is scaled according to OUT_SCALE from the value in
FIELD_VAL:
Indirect
Square Root
The block output is scaled according to OUT_SCALE from the value in
FIELD_VAL. Before the field value is rescaled, the square root is taken.
Uninitialized An invalid setting. The device reports a configuration error with an
Uninitalized L_TYPE.
OUT transducer_value=
OUT FIELD_VAL(OUT_SCALE.EU100-OUT_SCALE.EU0)()=
OUT OUT_SCALE.EU0
FIELD_VAL
100
--------------------------------+ OUT_SCALE.EU100 OUT_SCALE.EU0
()
=