5.10 Temperature Derating
None below 50 degrees C
DRNÐPSÐ750, 15mA per degree C above 50¡C
5.11 Power-on Indicator
Front Panel red LED lamp
5.12 Short-circuit and overload protection
DRNÐPSÐ750 foldback current limiting with automatic high
temperature shutdown
no fuses required
5.13 Wire Connections
Screw down wire clamps, AWG 12 to 26 (ferrules recommended
for stranded wire).
SPECIFICATIONS