12
RS-232 Communications Protocol & Command Set
BATTERY LEVEL STATUS
Requests the battery level, expressed as a percentage of maxi-
mum (full charge).
Send Query to UPS: ?BATTERYSTAT<CR>
Action: Load level will be displayed
Response: $BATTERY = xxx<CR>
xxx is the battery charge level (percentage of maximum charge)
expressed in decimal format. If the value is less than 100, the
hundreds digit is represented with a 0.
____________________________________________
LIST CONFIGURATION
Requests a list of all configurable parameters and current settings.
Send Query to UPS: ?LIST_CONFIG<CR>
Action: List of configurable parameters and
current settings will be displayed.
Response: $BTHRESH = level<CR>
$BUZZER = mode<CR>
$AVR = mode<CR>
$FEEDBACK = mode<CR>
LINEFEED = mode<CR>
$BRIGHTNESS = xxx<CR>
$SCROLL_MODE = xxx<CR>
$SLEEP_MODE = xxx<CR>
____________________________________________
List of all commands and queries
Send Query to UPS: ?HELP<CR>
Action: List of all commands and queries
will be displayed
Response: !ALL_ON<CR>
!ALL_OFF<CR>
!SWITCH<CR>
!SET_BATTHRESH<CR>
!SET_BUZZER<CR>
!SET_AVR<CR>
!SET_FEEDBACK<CR>
!SET_LINEFEED<CR>
!RESET_ALL<CR>
!SET_BRIGHT<CR> ?VOLTAGE<CR>
!SET_SCROLLMODE<CR> ?LOADSTAT<CR>
!SET_SLEEPMODE<CR> ?BATTERYSTAT<CR>
?ID<CR> ?LIST_CONFIG<CR>
?OUTLETSTAT<CR> ?HELP<CR>
?POWERSTAT<CR>
_________________________________________
RESPONSES & MESSAGES
OUTLET STATUS CHANGE
CONDITION RESPONSE
Outlet Bank 1 changes state $BANK1 = status<CR>
Outlet Bank 2 changes state $BANK2 = status<CR>
status = {ON, OFF}
_________________________________________
POWER BUTTON STATUS CHANGE
CONDITION RESPONSE
Power Button changes $BUTTON = status<CR>
ON/OFF status
status = {ON, OFF}
_________________________________________
POWER FAULT STATUS CHANGE
CONDITION RESPONSE
Overvoltage State $PWR = OVERVOLTAGE<CR>
Undervoltage State $PWR = UNDERVOLTAGE<CR>
Lost Power State $PWR = LOST POWER<CR>
Test Mode $PWR = TEST<CR>
Recovery Mode $PWR = RECOVERY<CR>
Normal Operation Mode $PWR = NORMAL<CR>
Low Battery $LOWBAT<CR>
AVR Stage $AVRSTATE = state<CR>
state = {BOOST, BUCK}
Remaining Backup Time $TIME = xxx<CR>
xxx = backup time
Battery State $BATTSTATE = xxx<CR>
xxx = {CHARGE, DISCHARGE, FULL}
Power Control Software
Complete Instructions are available by clicking on Help on the