Parker Hannifin R-507 Network Card User Manual


 
Evaporator
DI1
1- = Black
1S = Green
1+ = Red
R = Red
G = Green
W = White
B = Black
TS2 - Temp. Sensor 2
TS1 - Temp. Sensor 1
PB1 PB2
8.8.
Temperature
Sensor
SEI/SEH
TS2TS1 B W G R 1+ 1S 1- DI1
24 VAC
24 VAC
40 VA
Transformer
Pumpdown
Relay
(optional)
Pressure
Transducer
Valve 2 connections
on left block when used
SD-252-408
Pressing the UP button will increase the set point by 1 unit.
Pressing the DOWN button will decrease the set point by 1 unit.
Pressing the ENTER button will change the flashing digit from 1’s digit
to the 100’s digit.
Press and hold the UP button and ENTER button together for 5 seconds to
save the set point. The digits will stop blinking.
CHANGING REFRIGERANTS
Press and hold the UP button and ENTER button simultaneously for 5
seconds to enable the controller to change to another type of refrigerant.
All 4 digits will start to blink.
Pressing the UP button or the DOWN button will change the display to
other refrigerants.
When the display shows the desired refrigerant, press and hold the UP
button and ENTER button for together 5 seconds. The controller will save
and use the selected refrigerant’s table for saturated temperature. The digits
will stop blinking.
CHANGING VALVE TYPES – LGE1, SML1, or MED1
Press and hold the UP button and ENTER button for 5 seconds to enable
the controller to change to the other type of valves. All 4 digits will start
to blink.
Pressing either the UP button or the DOWN button will change the dis-
play between the different valve types. Press and hold the UP button and
ENTER button together for 5 seconds to save the selection. The digits
will stop blinking.
Pressing the UP button and the DOWN button simultaneously will toggle
the display between AC circuit 1 and AC circuit 2.
AC CIRCUIT 2 MENU
The preceding instructions apply to AC circuit 2 as well as AC circuit 1:
SUP2 Superheat read by controller for AC circuit 2
POS2 Number of steps valve is open (0-6386) for AC circuit 2
PRS2 Pressure read by the transducer (0-153 PSI, gauge) for AC
circuit 2
TMP2 Temperature read by the temperature sensor (-50 to 103°F) for
AC circuit 2
TST2 Saturated temperature for AC circuit 2
AC2, PDN2
AC2 when in normal operation, PDN2 when in pumpdown for
AC circuit 2
R22, 134A, 407C, 404A, R507
R22 for refrigerant R-22, 134A for refrigerant R-134a, 407C for
refrigerant R-407C, and 404A for refrigerant R-404A and R507
for refrigerant R-507. Note: Not all controllers have both
R-507 and R-407C.
LGE2, SML2, MED2, ESX2
LGE2 if the EEV used is an SEI-50 or larger for AC circuit 2.
SML2 if the EEV used is smaller than an SEI-25 for AC circuit 2.
MED2 if the EEV used is a SEI-25 for AC circuit 2.
ESX2 if the EEV used is a ESX for AC circuit 2.
SSP2 Superheat set point (0 to 16°F) for AC circuit 2. Default is
10°F.
MOP2 Maximum operating suction pressure set point (0 to 153 PSI)
for AC circuit 2. Default is 153 PSI.
CTS2 Cut out suction pressure set point for AC circuit 2 (0 to 153 PSI)
CLP2 Calibrate pressure transducer for AC circuit 2
CLT2 Calibrate temperature sensor for AC circuit 2
PRO2 Proportional gain set point for AC circuit 2. Number of steps
per degree that superheat is above or below the superheat set
point (5 to 255 steps per degree). Default is 45 for the LGE2
setting, 22 for the MED2 setting, or 11 for the SML2 setting.
INT2 Integral set point for AC circuit 2. Number of seconds the con-
troller waits to update the reference valve position. (1 to 120
seconds). Default is 10 seconds.
DER2 Derivative setpoint for valve 2. Advanced algorithm parameter
that determines the slope of the change control point. Default is
zero.
DON2 Time delay in seconds between end of pumpdown and com-
pressor start when Relay 1 is used to pilot the compressor con-
tactor. The pre-opens the valve before compressor start to avoid
nuisance low pressure safety trips. 2 seconds.
DOF2 Time in seconds that the valve is shut before the compressor
Relay 1 opens to stop the compressor. Allows refrigerant pump-
down/pumpout. Default is 2 seconds.
DST2 UsedwithDON2.Numberofstepstopre-openthevalvebefore
compressor start. Default varies with valve size.
Page 4
CHILLER P/T CONTROLLER WIRING SCHEMATIC*
© 2008 Sporlan Division, Parker Hannifin Corp., 206 Lange Drive, Washington, Missouri 63090
*Only valve 1 shown, valve 2 connected in similarly.