CHAPTER 1
INTRODUCTION
The Extended Battery Module (EBM) can be added to the
Powerware
5125 to extend the available UPS battery time (see Table 1).
Up to four EBMs can be installed with the Powerware 5125.
Table 1. Battery Run Times (in Minutes at Full/Half Load)
Model Internal UPS Batteries 1EBM 2EBMs 3EBMs 4EBMs
1000 VA 7/19 33/68 58/120 82/166 105/214
1500 VA 5/13 23/57 49/161 73/17 96/205
Battery times are approximate and vary depending on the load configuration and battery charge.
With the hot-swappable battery feature, UPS batteries can be added or
replaced easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power t o change the battery: 1) Press and
hold the Off
button until the long beep ceases (approximately five
seconds), then unplug the UPS; 2) Wait 60 seconds while the internal
processor shuts down before you disconnect the battery.