Powerware 300 VA Network Card User Manual


 
Troubleshooting
16
Powerware
®
3110 Users Guide S Rev B www.powerware.com
What to DoPossible CauseAlarm or Condition
1 beep every half second.
Power requirements exceed the
UPS capacity.
Remove some of the equipment from the UPS. You may
need to obtain a larger capacity UPS.
Output short circuit. Turn off or unplug the equipment connected to the UPS.
Input voltage is out of range
when the UPS is turned on.
Turn off the UPS until acceptable input voltage
restored.
Continuous beep.
UPS fault. Contact your service representative.
Service and Support
If you have any questions or problems with the UPS, call your Local
Distributor
or the Help Desk at one of the following telephone numbers
and ask for a UPS technical representative.
In the United States: 1
11
1-
--
-8
88
80
00
00
00
0-
--
-3
33
35
55
56
66
6-
--
-5
55
57
77
73
33
37
77
7 or 1
11
1-
--
-6
66
60
00
08
88
8-
--
-5
55
56
66
65
55
5-
--
-2
22
21
11
10
00
00
00
0
Europe, Middle East, Africa: +
++
+4
44
44
44
4-
--
-1
11
17
77
75
55
53
33
36
66
60
00
08
88
87
77
70
00
00
00
0
Asia: +
++
+8
88
85
55
52
22
2-
--
-2
22
28
88
83
33
30
00
0-
--
-3
33
30
00
03
33
30
00
0
Australia: +
++
+6
66
61
11
1-
--
-3
33
3-
--
-9
99
97
77
70
00
06
66
6-
--
-5
55
50
00
02
22
22
22
2
Please have the following information ready when you call the Help
Desk:
S Model number
S Serial number
S Version number (if available)
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information