Powerware 5140 Power Supply User Manual


 
Powerware
®
5140 Model Selection Guide
BATTERY RUN TIMES
STANDARD ONE ADDITIONAL TWO ADDITIONAL
LOAD BATTERIES EXTENDED BATTERY MODULE EXTENDED BATTERY MODULES
1000 Watts 1 hour 2 minutes 2 hours 24 minutes 3 hours 56 minutes
2000 Watts 28 minutes 1 hour 6 minutes 1 hour 47 minutes
3000 Watts 18 minutes 40 minutes 1 hour 6 minutes
4000 Watts 12 minutes 28 minutes 47 minutes
5000 Watts 8 minutes 21 minutes 36 minutes
6000 Watts 6 minutes 18 minutes 28 minutes
This table provides typical information. Battery times are approximate and may vary with equipment, configuration, disk access, battery use, temperature, etc.
REAR PANELS
PW5140 6000i
PW5140 6000
MODEL POWER OUT INPUT/OUTPUT FREQUENCY INPUT OUTPUT DIMENSIONS WEIGHT
NUMBER (VA/WATT)VOLTAGE (VAC)(HZ)CONNECTION RECEPTACLES (HXWXD)
1
(KG/LB)
(12) IEC-320, C13 & 10.5 x 17.25 x 24.3 in
PW5140 6000i 6000/6000 208/230
2
50/60
3
Hardwired (3) IEC-320, C19
4
26.7 x 43.8 x 61.7 cm 136/300
6
(2) L6-30R & 10.5 x 17.25 x 24.3 in
PW5140 6000 6000/6000 208/230
2
50/60
3
Hardwired (2) IEC-320
5
26.7 x 43.8 x 61.7 cm 136/300
6
Hardwired & 10.5 x 17.25 x 24.3 in
PW5140 6000 HW 6000/6000 208/230
2
50/60
3
Hardwired (2) IEC-320
5
26.7 x 43.8 x 61.7 cm 136/300
6
Options
Custom 5.25 x 17.25 x 22.5 in
PW5140 BATT Adapter 13.3 x 43.8 x 57.2 cm 81.6/180
Custom 1.98 x 19.28 x 9.90 in
PW5140 PDU
7
250/250 120 60 Adapter (2) 5-15R 5.03 x 48.97 x 25.15 cm 8.6/19
Adjustable; fits
PW5119 MK23 –––– standard 19-inch rack 4.5/10
1. 19-inch wide front panel with a 17.25-inch wide chassis; depth does not include front panel (.5 inches) 2. 208/230 Vac auto-sensing default. User-selectable via
LCD interface for 200, 208, 220, 230, and 240 Vac. 3. Automatic frequency synchronization. 4. Divided into 5 Load Segments. 5. Divided into 2 Load Segments;
IEC-320 receptacles are used to connect optional PW5140 PDU. 6. Shipping weight is 325 pounds (147 kg). 7. Sidewall design occupies 0U of rack space.
PW5140 6000 HW
China and North Asia
Hong Kong: 852.2745.6682
Australia and South Pacific
Sydney, Australia: 61.2.9878.5000
Canada
Toronto, Ontario: 416.798.0112
Powerware Corporation
Corporate Headquarters
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.877.797.9273 (PWRWARE)
or 919.872.3020
Fax: 1.800.753.9433
or 919.870.3411
E-mail: info@powerware.com
www.powerware.com
Latin America/Caribbean
Sunrise, FL: 954.835.1180
Europe/Middle East/Africa
Berkshire, England: 44.1753.606700
Southeast Asia
Singapore: 65.861.9877
A (2) INSTALLABLE OPTION SLOTS
B (2) COMMUNICATION PORTS
CMANUAL BYPASS SWITCH
D REPO PORT
EHARDWIRE INPUT
FLOAD SEGMENT 1
GLOAD SEGMENT 2
HLOAD SEGMENT 3
ILOAD SEGMENT 4
JLOAD SEGMENT 5
KCIRCUIT BREAKER(S)
L IEC-320 RECEPTACLES FOR PDU CONNECTION
MHARDWIRE OUTPUT
Revision 5140FXA 7/99
Reprint 7/99