Battery runtimes (in minutes)
iSeries pSeries Storage Cluster
870 890 655 670 690 2105 1350 1600
with
CEC + CEC + CEC + 1 2 3 expansion
I/O I/O I/O node nodes nodes up to 8 way 32 way standard enclosure
10 kVA 15 kVA 20 kVA 16 way 16 way 32 way 1 I/O 2 I/O 3 I/O 32 way 1 I/O 3 I/O
7 kW 10.5 kW 14 kW 6.8 kW 4.9 kW 8.3 kW 3.2 kW 6.4 kW 9.6 kW 6.5 kW 3.2 kW 10.5 kW 6.4 kW 13.8 kW
Internal battery 45 26 17 48 79 31 110 50 27 49 110 26 50 17
(1) External
battery cabinet 90 65 48 98 150 75 240 110 70 108 240 65 110 48
(2) External
battery cabinets 155 90 75 166 240 130 400 180 96 172 400 90 180 75
Contact Powerware for runtime, application or configuration assistance.
A DC rated circuit breaker in each battery cabinet allows
multiple battery strings to be serviced independently of each
other, assuring back up power is always available to the UPS
Removable battery slide-out tray assembles provide “front
access only” and reduce battery maintenance time.
Manufacturer-supplied wiring with quick disconnects provides
plug-and-play capability for line-up and match configurations.
Quick disconnects between battery tray assemblies reduce
battery maintenance time.
Ī
Battery cabinets may be daisy-chained together for extended battery runtimes,
(up to 2).
Ī
Integral configuration, which line up and match, is standard.
1
Ī
Front-access-only enhances servicing and installation.
Ī
Slide trays and modular battery packaging makes periodic servicing easy.
Ī
Cabinets are UL 1778 listed.
Ī
Flame retardant batteries meet UL 94V2 for computer room installations.
Ī
Wiring installation.
2
Powerware offers a full line of battery cabinets for the Powerware P93.
Extended Battery Cabinets
1. Battery cabinets can be configured as line up and match or
remotely located. Customer must provide wiring for remotely
located cabinets. 2. If concurrent to P93 Field Installation,
Powerware PN 103003671, IBM PN 97P3604.
Calculating runtime - a guide
Typical runtime is 15 minutes
Formula (runtime in minutes) = [business + (2 x system shutdown) + safety]
Business = _____
Shutdown ____ x 2 = _____
Safety = _____
Total = _____
Powerware IBM IBM Per P93
Part Number Feature Code Part Number Minimum Maximum
External Battery Cabinet A13031 6635 97P2663 0 2
Additional options
Ī
Input/output galvanic isolation
Ī
Voltage matching transformers
Ī
Remote status panel
Ī
Remote EPO button
Contact