Powerware UPS20-30kVA Power Supply User Manual


 
31UPS 20-30 kVA, 230 V 50/60 Hz output
User’s Guide
1026743
Revision B
Battery information and settings:
ABM charging cycling disable [Enabled], [Disabled] Enabled
Charging temp compensation [Enabled], [Disabled] Enabled
Battery size setting Step: 1 Watts/cell 24 Watts/cell
Number of 36 pcs. battery strings 0 (no batteries), 1, 2, 3, 4... 1 string
Battery low alarm level Step: 0.01 V/cell 1.88 V/cell
Automatic battery support test [Enabled], [Disabled] Enabled
Maximum charging current Step: 0.1 A [max. 25 Amps] 6 Amps
Output on, automatic delay time before turning
the output on
[Disabled], [Set delay, step: 1 sec] 0 sec.
Output off, automatic delay time on battery
after which output is turned off
[Disabled], [Set delay, step: 1 sec] Disabled
User preferences:
Operation priority while rectifier input break [On battery], [On bypass] On battery
Site wiring fault w/ wrong Neutral connection [Enabled], [Disabled] Enabled
Power Strategy [Standard], [High Efficiency] Standard
Parallel settings:
Parallel unit number
[Single unit], [Unit #1], [Unit #2], [Unit #3],
[Unit #4]
Single unit
Parallel operation mode [Redundant mode], [Capacity mode] Redundant mode
Synchronization [Enabled], [Disabled] Enabled
Start auto calibration
Parallel XCP [System], [Unit] System
Minimum units to support load [0], [1], [2], [3], [4] 2
Table 5 User setting in the LCD menu screen.