Rackmount Solutions E1500RM1U Power Supply User Manual


 
20
English
Default 120VAC User selectable 120/127VAC
700VA
490W
1500VA
900W
1000VA
700W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
Sine Wave
Frequency
50/60Hz, +/-0.1Hz (unless synchronized to utility)
Nominal Voltage
Maximum Power Capacity
2-6 mS Typical
>93% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-6Hz, autosensing
0 - 165VAC
85 - 150VAC
120VAC: 105 - 132VAC (127VAC: 105 - 137VAC)
Transfer Time
Efficiency (Line Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
E1500RM1U
E1000RM1U
E700RM1U
Model Number
SYSTEM SPECIFICATIONS
Voltage Range
Topology
Line-Interactive, Sine Wave
OUTPUT NON-BATTERY OPERATION
INPUT
Number of Phase Single (1 2W +G)
Nominal Voltage 120VAC
Low Voltage Transfer Point
85V resets to Utility Power at 90V or higher
High Voltage Transfer Point
150V resets to Utility Power at 145V or lower
Voltage Regulation
120VAC: -12.5% - +10% (127VAC: -17.3% - +7.8%)
Frequency Range 60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz
OUTPUT BATTERY OPERATION
Voltage Regulation Nominal +/-2% (until Low Battery Warning)
Voltage T.H.D.
<5% (Linear Load)
+/-5% @ 100% Load change in 100mS
Dynamic Response
Slew Rate
<1Hz/Second
Overload Capacity
110% for 20-Seconds
125% for 10-Seconds
150% Shutdown Immediately
<8% (Linear Load)