Rackmount Solutions VA 1000 Power Supply User Manual


 
22 Chloride Active and E-Series UPS User Manual
Chapter 10 Active Tower and Rackmount Specifications
Table 5. Chloride Active UPS North America
UPS Model Active 700 Active 1000 Active 2000 Active 3000
Electrical Data
Rating 700 VA 1 kVA 2 kVA 3 kVA
Input
Voltage 120 VAC single-phase
Voltage range A 80 - 138 VAC
Frequency 50/60Hz ± 0.5%
Power factor (lambda) >0.95
Battery
Integrated battery type Lead-calcium, maintenance-free
Battery voltage (V) 24 36 96 96
Runtimes (min.)
(half load/full load)
10/5 15/6 18/7 10/5
Runtimes (min.),1 battery cabinet
(half load/full load)
NA 70/30 100/30 60/30
Runtimes (min.), 2 battery cabinets
(half load/full load)
NA 130/60 200/80 120/50
Output
Voltage 100/110/120 VAC, single-phase
Voltage tolerance ± 3%
Frequency with mains control see input frequency
Frequency with internal control 50/60 Hz, ±0. 5%
Distortion factor (linear/non-linear load) max. 4%/max. 7%
Permissible crest factor 3
Overload capability
130% for 1.5 sec., 110% for 10 sec.
output short-circuit proof
Common Data
Electrical safety UL1778
Radio interference level FCC Part 15 Class A
Interference immunity
IEC 801-2,level 4 / IEC 801-3,level 3;
IEC 801-4,level 4 / IEC 801-5,level 2)