RuggedCom RS930L Switch User Manual


 
www.RuggedCom.com
6
RuggedVDSL
TM
RS930L
RuggedVDSL™ RS930L
6-Port Managed Ethernet Switch with Dual Port Ethernet over VDSL Uplinks
EMI and Environmental Type Tests
Notes: 1. Class 2 refers to "Measuring relays and protection equipment for which a very high security margin is required or where the vibration levels are very high, ( e.g. shipboard application and for severe transportation conditions")
Environmental Type Tests
Test Description Test Levels Severity Levels
IEC 60068-2-1 Cold Temperature Test Ad -40°C, 16 Hours N/A
IEC 60068-2-2 Dry Heat Test Bd +85°C, 16 Hours N/A
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db
95% (non-condensing), 55°C , 6
cycles
N/A
IEC 60255-21-1 Vibration Tests Fc 2g @ (10 - 150) Hz Class 2
IEC 60255-21-2 Shock Tests Ea 30g @ 11mS Class 2
IEC 61850-3 EMI TYPE TESTS
TEST Description Test Levels Severity Levels
IEC 61000-4-2 ESD
Enclosure Contact +/- 8kV 4
Enclosure Air +/- 15kV 4
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m x
IEC 61000-4-4 Burst (Fast Transient)
Signal ports +/- 4kV @ 2.5kHz x
D.C. Power ports +/- 4kV 4
A.C. Power ports +/- 4kV 4
Earth ground ports
3
+/- 4kV 4
IEC 61000-4-5 Surge
Signal ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
D.C. Power ports +/- 2kV line-to-earth, +/- 1kV line-to-line 3
A.C. Power ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
IEC 61000-4-6 Induced (Conducted) RFI
Signal ports 10V 3
D.C Power ports 10V 3
A.C. Power ports 10V 3
Earth ground ports
3
10V 3
IEC 61000-4-8 Magnetic Field Enclosure ports 40 A/m continuous, 1000 A/m for 1 s N/A
IEC 61000-4-29
Voltage Dips & Interrupts
D.C. Power ports 30% for 0.1s, 60% for 0.1s, 100% for 0.05s N/A
A.C. Power ports
30% for 1 period, 60% for 50 periods N/A
IEC 61000-4-11
100% for 5 periods, 100% for 50 periods
2
N/A
IEC 61000-4-12 Damped Oscillatory
Signal ports 2.5kV common, 1kV diff. mode@1MHz 3
D.C. Power ports 2.5kV common, 1kV diff. mode@1MHz 3
A.C. Power ports 2.5kV common, 1kV diff. mode@1MHz 3
IEC 61000-4-16 Mains Frequency Voltage
Signal ports 30V Continuous, 300V for 1s 4
D.C. Power ports 30V Continuous, 300V for 1s 4
IEC 61000-4-17 Ripple on D.C. Power Supply D.C. Power ports 10% 3
IEC 60255-5 Dielectric Strength
Signal ports 2kVac (Fail-Safe Relay output) N/A
D.C. Power ports 2kVac N/A
A.C. Power ports 2kVac N/A
IEC 60255-5 H.V. Impulse
Signal ports 5kV (Fail-Safe Relay output) N/A
D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A
IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS
Test Description Test Levels Severity Levels
IEEE C37.90.3 ESD
Enclosure Contact +/- 8kV N/A
Enclosure Air +/- 15kV N/A
IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m N/A
IEEE C37.90.1 Fast Transient
Signal ports +/- 4kV @ 2.5kHz N/A
D.C. Power ports +/- 4kV N/A
A.C. Power ports +/- 4kV N/A
Earth ground ports3 +/- 4kV N/A
IEEE C37.90.1 Oscillatory
Signal ports 2.5kV common mode @1MHz N/A
D.C. Power ports 2.5kV common, 1kV diff. mode@1MHz N/A
A.C. Power ports 2.5kV common, 1kV diff. mode@1MHz N/A
IEEE C37.90 H.V. Impulse
Signal ports 5kV (Fail-Safe Relay output) N/A
D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A
IEEE C37.90 Dielectric Strength
Signal ports 2kVac N/A
D.C. Power ports 2kVac N/A
A.C. Power ports 2kVac N/A