Schneider Electric 66074 Network Card User Manual


 
Network
Management Card
User Manual
Network Management Card
– User Manual 34003676EN/HA
Page
63/81
4.2.2 Extended power outage, shutdown initiated by the “Low battery power”
message
When the ”Low battery power” message is displayed, the UPS is shut off after taking into account the shutdown
duration of the servers.
“Low battery power”: The message appears if either of the two following criteria is checked:
- Low Battery Level
- Minimum remaining backup time (Low Battery Delay)
Utility OFF
Trap 17
Trap 11
Trap 29
Low
battery
Trap 9
Trap 18
Trap 10
Trap 31
Shutdown
Duration
Trap 32
NSM Shutdown
Rebo
ot
UPS output OFF