Schneider Electric 66123 Network Card User Manual


 
Network Management Card & Modbus/Jbus 34022321XT indice :AE Page 96/98
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
11.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11)
SNMP traps are sent when alarms appears and desappears.
Level : 1:informational , 2:major, 3:critical
MIB TRAP Trap # niveau
-upsmgBatteryFault (Nota1) Trap 1 Level 3
-upsmgBatteryOK (Nota1) Trap 2 Level 1
-upsmgAtLowBattery (Nota1) Trap 5 Level 3
-upsmgFromLowBattery (Nota1) Trap 6 Level 1
-upsmgChargerFault (Nota1) Trap 7 Level 3
-upsmgChargerOK (Nota1) Trap 8 Level 1
-upsmgOnBattery (Nota1) Trap 11 Level 2
-upsmgReturnFromBattery (Nota1) Trap 12 Level 1
-upsmgOnByPass Trap 13 Level 2
-upsmgReturnFromByPass Trap 14 Level 1
-upsmgUtilityFailure Trap 17 Level 2
-upsmgUtilityRestored Trap 18 Level 1
-upsmgOverLoad Trap 21 Level 3
-upsmgLoadOK Trap 22 Level 1
-upsmgOverTemperature (Nota1) Trap 23 Level 3
-upsmgTemperatureOK (Nota1) Trap 24 Level 1
-upsmgOffInProgress (Nota1) Trap 31 Level 3
-upsmgCommunicationFailure Trap 37 Level 3
-upsmgCommunicationRestored Trap 38 Level 1
-upsmgRedundancyLost Trap 65 Level 2
-upsmgRedundancyOK Trap 66 Level 2
-upsmgProtectionLost Trap 67 Level 2
-upsmgProtectionOK Trap 68 Level 2
Nota1: This Information is not present with a Static Switch Cabinet unit.
If the Environment Sensor is detected , the following information are managed.:
- upsEnvironmentComFailure Trap 53 Level 2
- upsEnvironmentComOK Trap 54 Level 2
- upsEnvironmentTemperatureLow Trap 55 Level 2
- upsEnvironmentTemperatureHigh Trap 56 Level 2
- upsEnvironmentTemperatureOK Trap 57 Level 2
- upsEnvironmentHumidityLow Trap 58 Level 2
- upsEnvironmentHumidityHigh Trap 59 Level 2
- upsEnvironmentHumidityOK Trap 60 Level 2
- upsEnvironmentInput1Closed Trap 61 Level 2
- upsEnvironmentInput1Open Trap 62 Level 2
- upsEnvironmentInput2Open Trap 64 Level 2
- upsEnvironmentInput2Closed Trap 63 Level 2
The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified applications” page