SMC Networks EX9-AC -1 Switch User Manual


 
24 25
Part Names
Tie-rod (2 pcs.)
Accessory
Tie-rod (2 pcs.)
Accessory
Waterproof cap
(for socket)(1 pc.)
Dimensions ( unit : mm )
59.8
72.6
21
Output Block
59.8
80.3
21
PWR
PWR
Power Block
Mounting/Installation
Refer to subsection "Mounting/Installation" (page 7) in this manual.
Specifications
Model No. EX9-OET1 EX9-OEP1
Power supply
type
Internal power supply type
External power supply type
(Supplied from the Power Block,
EX9-PE1.)
Rated voltage 24VDC
Output method PNP output (-COM.)
Rated load
current
Max. 62mA/point
Max. 0.5A/point
NOTE)
* It is limited to the max. Power Block supply current 3.1A.
Output Block
Output Block
Power Block
Output equipment connector1 Connects with output device.
Note1)
Operation display LED
2
Indicates the output status.
Note2)
Part names
No.
Application
Note1 : For wiring method, refer to subsection "Wiring" (page 26) of section "EX9 Series Output
Block/Power Block" in this manual.
Note2 : For display, refer to subsection "Display" (page 30) of section "EX9 Series Output
Block/Power Block" in this manual.
Note1 : For wiring method, refer to subsection "Wiring" (page 28) of section "EX9 Series Output
Block/Power Block" in this manual.
Note2 : For display, refer to subsection "Display" (page 30) of section "EX9 Series Output
Block/Power Block" in this manual.
Power supply connector1
Power can be supplied to SI Unit when connecting
SI Unit next to Power Block.
Note1)
Power input connector
2
Supplies power for output devices.
Note1)
Operation display LED
3
Indicates the power supply status.
Note2)
Part names
No.
Application
NOTE
When connecting an inductive load such as a solenoid valve or relay without built-in surge sup-
pressor, the use of an external surge suppressor is recommended.