Display Description
PWR
Lights up Power supply for sensor is ON.
Off Power supply for sensor is OFF.
0, 1, 2, 3
Lights up Sensor signal input corresponding to the number is ON. (Logic "1")
Off Sensor signal input corresponding to the number is OFF. (Logic "0")
Switch setting
Applicable sensor to the Input Block can
be switched to NPN/PNP.
Remove the Input Block according to the
"Mounting/Installation" (Page 7) in this
operation manual, then set up the switch
with a sharp-pointed watchmakers screw
driver etc.
Install the Input Block after the setting
according to "Mounting/Installation"
(Page 7) in this operation manual.
NPN/PNP selector switch
NPN
PNP
EX9 OE 1
Power supply type
T
P
Internal power supply type (for low wattage load)
External power supply type (for high wattage load)*
* It is connected to the Power Block while its operation.
Output specification
1
PNP output (-COM.)
EX9 PE1
Display
The EX9 series General Purpose Output Block is the unit to operate various output
(solenoid valve, relay, etc.) in combination with valve and SI Unit.
There are two types ---- one type is for low wattage load (EX9-OET1) receiving power
supply from SI Unit, and the other type is for high wattage load (EX9-OEP1) receiving
power supply from an external source.
NOTE)
The type for high wattage load is used in combination with the Power Block (EX9-PE1)
connected with external power supply.
As the low wattage load type is powered from SI Unit, the wattage of load is limited to
1.5W
NOTE)
. For a load up to 12W, use the Power Block and the high wattage load type.
Output Block
Power Block
EX9 Series Output Block/Power Block
Model Indication Method
NOTE
+COM. type EX9-OET/P2 cannot be connected to EX250-SEN1.