2-4
SUPERSERVER 5014C-T User's Manual
Figure 2-1. Identifying the Sections of the Rack Rails
Mounting Holes
A
Locking Tab
B
2-4 Installing the System into a Rack
This section provides information on installing the SuperServer 5014C-T into
a rack unit. If the system has already been mounted into a rack, you can
skip ahead to Sections 2-5 and 2-6. There are a variety of rack units on the
market, which may mean the assembly procedure will differ slightly. The
following is a guideline for installing the unit into a rack with the rack rails
provided with the system. You should also refer to the installation instruc-
tions that came with the rack unit you are using.
Identifying the Sections of the Rack Rails
You should have received two rack rail assemblies with the SuperServer
5014C-T. Each of these assemblies consist of two sections: an inner fixed
chassis rail that secures to the unit (A) and an outer fi xed rack rail (B) that
secures to the rail brackets. A sliding rail guide sandwiched between the
two should remain attached to the fixed rack rail (see Figure 2-1). The A
and B rails must be detached from each other to install.
To remove the fixed chassis rail (A), pull it out as far as possible - you
should hear a "click" sound as a locking tab emerges from inside the rail
assembly and locks the inner rail. Then depress the locking tab to pull the
inner rail completely out. Do this for both the left and right side rack rail
assemblies.