ATTENTION:
Risque de choc et de danger e'lectriques. Le de'branchement d'une seule alimenttation stabilise'e ne de'branche uniquement
qu'un module "Alimentation Stabilise'e".
Pour isoler completement le module en cause, il faut de'brancher toutes les alimentations stabilise'es.
SAFETY SYMBOLS
CAUTION Risk of Electrical Shock.
Instruction manual symbol. The instrument will be marked with this symbol when it is
necessary for the user to refer to the instruction manual.
Indicates hazardous voltage.
Indicates ground terminal.
Protective Ground Conductor Terminal
Denotes hazard. An attention to a procedure is called. Not following the procedure correctly
could result in personal injury. A WARNING sign should not be skipped and all indicated
conditions must be fully understood and met.
Denotes hazard. An attention to a procedure is called. Not following the procedure correctly
could result in damage to the equipment.
ENERGY HAZARD
The FPS1000, FPS-S1U and the FPS-T1U products are capable of providing hazardous energy.
Manufacturers final equipment must provide protection to service personnel against inadvertent contact with these models
output terminals. If set such that hazardous energy can occur then the output terminals or connections therefore must not
be user accessible.
OVERCURRENT PROTECTION:
A readily accessible Listed branch circuit overcurrent protective device rated 20 A must be incorporated in the building wiring.
SERIAL OPERATION
The FPS-T1U product is capable of providing hazardous voltage output in case of the serial connection of two or more FPS1000
units in the rack. Manufacturers final equipment must provide protection to service personnel against inadvertent contact with
these models output terminals. If set such that hazardous voltage can occur then the output terminals or connections therefore
FUSES
There are no user replaceable fuses in the FPS1000, FPS-S1U and the FPS-T1U products. Internal fuses are sized for fault
protection and if a fuse was opened it would indicate that service is required. Fuse replacement should be made by qualified
technical personnel.
FPS-S1U and FPS-T1U racks contains no fuses. FPS1000 fuses rating are described below.
F101: F20A H 250Vac
F102: 6.3A 400Vdc
SICHERHEITSHINWEISE
Vor Anschluss an die Netzversorgung ist die Aufstellanleitung zu beachten!
1. Absicherung: F101: F20A H 250VAC, F102: 6.3A 400VDC
2. Der maximale Ableitstrom der Gesamtanlage darf 3.5mA nicht ueberschreiten.
3. Die Gehaeuseabdeckung darf nur im stromlosen Zustand geoeffnet werden.
ACHTUNG: