TOA Electronics FPS-T1U Power Supply User Manual


 
25
CHAPTER 9 FPS-S1U RACK SPECIFICATIONS
FPS-S1U Instruction Manual
Notes:
*1: The Output of all the FPS1000 modules are connected in parallel in the rack.
*2: For input voltage lower than 100Vac, maximum output power derated by 10% of the power rating.
*3: For cases where conformance to to various safety standards (UL, EN etc.) is required, to be described
as 100-240Vac (50/60Hz).
*4: Remote sensing can compensate up to 1V drop on each load wire.
*5: Not apllicable for units with I
2
C bus option.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Number of power supply modules (*1)
Maximum output power (*2)
Input voltage / frequency range (*3)
Maximum input current (at 100/200Vac)
AC input connector
Output terminals
Remote sensing (*4)
Parallel operation
Series operation (*5)
Remote On/Off control
DC_OK signal
AC fail signal
Over Temperature alarm signal
Vout voltage trimming
Auxiliary power supply
Operating temperature
Storage temperature
Operating humidity
Storage humidity
Vibration
Shock
Applicable safety standards
Withstand voltage
Insulation resistance
Weight (Typ)
Size (W*H*D)
Warranty
---
W
---
A
---
---
V
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
Kg
---
Yr
Maximum 3 x FPS1000 modules of the same output voltage rating.
3000
85~265Vac continuous, 47~63Hz, Single phase
12.0/6.0 for each FPS1000 unit installed
FPS-S1U :IEC inlet for each power supply module . FPS-S1U/P :None
Bus-bars.Refer to outline drawing.
Possible.
Possible. Up to 3 racks with max 8 FPS 1000 units of the same voltage and current rating.
Possible. Up to 2 racks of the same voltage and current rating
Separate control for each FPS 1000 unit , By electrical signal or dry contact
ON: 0~0.6V or short. OFF: 2~15V or open.
Separate control for each FPS1000 unit, Open collector signal.
On when Vout >80% +/-5%. Max.sink current: 10mA
Separate control for each FPS1000 unit ,Open collector signal.
Refer to Instruction Manual
Separate control for each FPS1000 unit ,Open collector signal.
Refer to Instruction Manual
Possible, via separate control for each FPS1000 unit .Refer to Instruction Manual.
11.2~12.5VDC.Maximum output current:0.25A*Number of installed FPS1000 units.
0~50°C: 100% load. Derate 2%/°C, 50°C to 60°C.
-30~85°C
10~90% RH, no condensation.
10~90% RH, no condensation.
Built to meet ETS 300 019
Built to meet ETS 300 019
UL60950-1, EN60950-1
Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground:
500Vrms, 1min.
More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc
3.7
440x44x351mm. Refer to Outline Drawing.
Two Years