Frequency Regulation ± 0.25Hz
Wave Form Sine wave, Zero Transfer Time
Load Power Factor 0.7
Efficiency AC to AC Greater than 86%
BATTERY DC Voltage 36V
Backup Time 7 min (full load) 21 min (half load)
Battery type Yuasa Flame Retardant Lead Acid 9Ah/12V
Number of batteries 3
Recharge time <4 hours to 90%
PHYSICAL Interface RS-232, USB Standard, Option Card Interface, Network Transient Protector, External Battery Connectivity
Line Cord 5-15R
Receptacles Six NEMA 5-15R
Dimensions WxDxH (mm) 420x152x239
Ship Dimensions WxDxH (mm) 546x280x356
Dimensions W x D x H (inch) 16.5x6x 9.4
Ship Dimensions WxDxH (inch) 21.5x11x14
Weight kg (lb) 16.2 (35.6)
Ship Weight kg (lb) 18.2(40)
OPTION External Matching Battery Cabinet Single - 25 Mins, Double - 50 Mins. Max Two Cabinets. Part #: UT1-BC-0125
Remote Contact Card Part #: UT1-RMT-CONTACT
Network Interface Card RemotEye II - Part #: RMTI-INT-R4
Environmental Monitoring Device Part #: RMTI-EMD-HT
Frequency Conversion Software Package Part # DUM0029
ENVIRONMENT Operating Ambient Temperature 0 ~ 40
o
C (32 ~ 104
o
F)
Recommended Temperature +15
o
C ~ 25
o
C
Storage Temperature -15
o
C ~ 50
o
C
Cooling Forced Air-Cooling
Humidity 0-95%, Non-Condensing
Audible Noise Less than 45db Normal and Battery Modes
Altitude 11500 ft (3,500 m) above sea level
CONFORMANCE Regulatory Approvals FCC Part 15 Class B, UL 1778, ICES-003
WARRANTY Three years on electronics
Two years full replacement on battery (See Toshiba warranty policy for full details)