Toshiba 125 Power Supply User Manual


 
107
G8000 Series Installation and Operation Manual
Insert Belleville washer between at washer and nut.
8. Connect the Control plug/connector (male) located in input cabinet to the mating
connector (female) in the output cabinet thru conduit plate in the side panels. See
FIG. 5 & FIG. 6.
9. Connect the Ground cable located in input cabinet to the Ground Bus located in the
output cabinet thru the grommet hole in the side panels.
NOTE: SEE MANUAL PAGE 38 FOR CONNECTING POWER CABLES & ANCHOR-
ING THE CABINETS TO THE FLOOR. AFTER CONNECTING THE CABLES.
ENSURE NO LOOSE HARDWARE, METAL SHAVINGS, TOOLS, ETC. ARE LEFT BE-
HIND INSIDE THE CABINET.
CLOSE THE CABINETS FRONT AND BACK. RECOMMENDED TORQUE VALUES OF
3/8” STEEL BOLT IS 220 IN-LBS, 1/2” STEEL BOLT IS 390 IN-LBS.
NEUTRAL BUS
AC BUS
DC BUS
CONTROL CONNECTOR
(FROM INPUT CABINET)
FIG. 5