Toshiba 150 Power Supply User Manual


 
29
G8000 Series Installation and Operation Manual
10.3 Anchor Bolts
Install the anchor bolts to secure the UPS on the oor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base.
See Figure 10.3 for the hole locations and dimensions for the specied UPS models.
4 x 5/16 in. (16 mm)
diameter screw holes
4 screw holes
(Side View)
Anchor Bolt
FIGURE 10.2
ANCHOR BOLT INSTALLATION DETAIL
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS
ON BOTTOM OF UPS
Back
Front
4 x 0.5 in. - Dia. (12 mm)
29.7 in. (755 mm)
21.7 in.
(551 mm)
80/100/125 kVA
(See Appendix B)
21.7 in.
(551 mm)
Back
Front
4 x 0.5 in. - Dia. (12 mm)
46.1 in. (1171 mm)
150/225 kVA
(See Appendix B)
25.6 in.
(650 mm)
Back
Front
8 x 0.5 in. - Dia. (12 mm)
22.5 in.
(571 mm)
300 kVA
(See Appendix B)
22.5 in.
(571 mm)
22.5 in.
(571 mm)
500 kVA
(See Appendix B)
30.0 in.
(762 mm)
Back
Front
12 x 0.5 in. - Dia. (12 mm)
33.9 in.
(862 mm)
20.0 in.
(508 mm)
22.4 in.
(568 mm)
20.0 in.
(508 mm)
3.0 in. (76 mm)
Input Section
Output Section