Toshiba 1800 Power Supply User Manual


 
1800 Series Single Phase Uninterruptible Power Systems
Product Specifications – Rev 3.0 August 2008
2.4 kVA
Page 6 of 6
12.0 Environment Operation
Operating Ambient Temperature: 0 ~ 40
o
C (32 ~ 104
o
F)
Recommended Temperature: +15
o
C ~ 25
o
C
Storage Temperature: -20
o
C ~ 40
o
C
Humidity: 30-90%, Non-Condensing
Audible Noise: 50dB (A) maximum @ 1 meter from Front Panel
Altitude: 1000 m (3,000 ft) above sea level
13.0 Conformance
UL 1778, CUL, CE, FCC Part 15 Class A
14.0 Warranty
Toshiba Standard warranty includes 3 Years of on site service which covers electronics
and labor, and a 5 year warranty on the batteries (2 years full, 3 years pro-rated)
15.0 Options
15.1 Remote Monitoring
The UPS contains a communication slot this allows the operator to field install an
optional RemotEye II card. The RemotEye II card allows the UPS to communicate via
Ethernet SNMP, connected directly to the Local Area Network. SNMP/ Web based
monitoring – Toshiba UPS system provides comprehensive monitoring of the UPS
operation. The optional RemotEye II features an HTTP (web-based) interface for
Toshiba UPS. This allows easy access to the Toshiba UPS information from any
PC/Network with a web browser.
15.2 Environmental Monitoring Device (EMD)
The EMD is an environmental monitoring device that provides remote monitoring of
temperature, humidity and other environmental conditions via standard web browser or
network management systems. The EMD provides automated events notification when
temperature, humidity or user defined dry contacts is out of configured tolerance.