G8000 Series Installation and Operation Manual
12 UPS Specications
12.1 Specication Table
G8000 Specications
Model Number
T80S3K08
KK6XSxx
T80S3K10
KK6XSxx
T80S3K12
KK6XSxx
T80S3K15
KK6Xxx
T80S3K22
KK6XSxx
T80S3K30
KK6XSxx
T80S3K50
KK6XSxx
Input
Rated Output
Capacity
80 kVA /
80 kW
100 kVA /
100 kW
125 kVA /
100 kW
150 kVA /
150 kW
225 kVA /
225 kW
300 kVA /
300 kW
500 kVA /
450 kW
Voltage 480 VAC (+10% to -15%)
Frequency 60 Hz (+/-5%)
Conguration 3 Phase; 3 Wire + GND
Input kVA
Normal (Charging)
89 kVA
(100 kVA)
111 kVA
(122 kVA)
112 kVA
(123 kVA)
163 kVA
(174 kVA)
247 kVA
(258 kVA)
329 kVA
(340 kVA)
484 kVA
(505 kVA)
Power Factor > 0.99 PF Lagging
Walk-in Function EEPROM Upgrade
Maximum Input
Current
Normal (Charging)
107 A
(120 A)
134 A
(147 A)
135 A
(148 A)
196 A
(209 A)
297 A
(311 A)
396 A
(409 A)
582 A
(608 A)
Reected THD < 5% @ 100% Load
< 6% @ 25% Load
Bypass
Conguration 3-Phase; 4-Wire + Gnd
Voltage 480/277V (±10%)
Frequency 60 Hz (+/-5%)
Bypass Overload
Capacity
1000% for 1 Cycle, 500% for 2 Cycle
Battery
Number of Cells 180 240
Type Lead Acid (Contact factory for alternative options)
DC Nominal 360V 480V
DC Minimum 288V 408V
Float Charge 405V 540V
Ripple Current
(without batteries)
AC Ripple on DC Bus: < 0.2% of DC Voltage
Back-up Time Application Specic
Max DC Charging
Current
30 A 30 A 30 A 30 A 30 A 30 A 45 A
Max Discharge 292 A 359 A 365 A 533 A 805 A 1073 A 1193 A
Battery Capacity
Required for Full
Load Output
88 kWB 108 kWB 110 kWB 160 kWB 242 kWB 323 kWB 478 kWB