Toshiba 300 Power Supply User Manual


 
65
G8000 Series Installation and Operation Manual
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
UPS SUPPLY
AC - Vo 480 v
AC - Io 50%
14.4 Switch Power Supply (UPS to Bypass)
The procedure to transfer between the UPS supply and the bypass supply is shown in Steps 1-3
STEP 1
Check AC INPUT LED and BYPASS LED are
on to make sure power is being delivered to
the UPS.
STEP 2
Press the “BYPASS” button for at least 0.5
seconds.
UPS LED is “OFF”.
BYPASS LED is “ON”.
STEP 3
Please wait until procedure is completed.
NOTE
To change from Bypass to UPS supply, follow
the Startup Procedures - STEP 5.
If the AC switch does not function, contact
Toshiba or authorized representatives.
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
BYPASS
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
BYPASS
AC - Vo 480 V
AC - Io 50%
PRESS ‘UPS’ SWITCH
LED Key
- LED Off
- LED On
- LED Flash