Toshiba 480 Power Supply User Manual


 
52
G8000 Series Installation and Operation Manual
12.2 Typical Efciency vs. Load
UPS Efciency at Percent Full Load*
25% 50% 75% 100%
80 kVA 83.9% 85.3% 90.0% 90.6%
100 kVA 86.4% 90.1% 91.2% 91.0%
125 kVA 88.5% 90.9% 90.9% 90.2%
150 kVA 86.9% 91.7% 92.3% 93.3%
225 kVA 87.9% 91.9% 92.3% 91.9%
300 kVA 88.8% 91.6% 92.2% 92.8%
500 kVA 91.6% 91.1% 90.2% 93.3%
* Actual efciency may differ due to manufacturing variations and input power quality.