Toshiba DEV002Z Network Card User Manual


 
E6581295
- 14 -
5.1. f851: Communication Loss Action Setting (Network breaks)
This parameter sets up the VF-AS1/PS1 response to a loss of communications with the
DeviceNet network.
0: Stop and Communication release
The inverter decelerates the motor to a stop and gives an alarm (the leftmost LED
flashes). Commands entered through the network are canceled, and the commands
set with parameters cmod and fmod become effective.
When communications are restored, the alarm is turned off.
1: None
The inverter remains in the state where it was when the problem arose, and it gives an
alarm.
2: Deceleration stop
The inverter decelerates the motor to a stop and gives an alarm. Commands
entered through the network are not canceled.
3: Coast stop
The inverter issues a command for a frequency of 0Hz and gives an alarm.
Commands entered through the network are not canceled.
4: Emergency stop
The error message err8 is displayed. Commands entered through the network are
not canceled.
When communications are restored, the inverter is not restored to working order and
the error message err8 does not disappear until the inverter is reset.
5: Preset speed operation command
Refer to Section 5.2
5.2. f852: Preset speed operation selection
If the communication loss action (parameter f851) is set to 5 (preset speed command),
the VF-AS1/PS1 will run at a preset speed as set up by this parameter in the case of a
communication loss (with alarm). Commands entered through the network are not canceled.
For example,
If the inverter is set as described below,
f851 = 5 (preset speed operation command)
f852 = 8 (preset speed operation frequency 8)
f287 (preset speed operation frequency 8) = 10 (10Hz)
Operation is carried out as follows.
Network Operation of the VF-AS1/PS1
Normal conditions...........Operates according to commands entered through the network.
communications loss ......Operates at 10Hz.
Restoration......................Operates according to commands entered through the network.