3.4.6.11. FE36 (Analog input value VI/II)
The value inputted into the VI/II terminal is read.
The value range is 0x0 to 0x2710 (0 to 100.00 %).
- Also about FE35 (RR Input), it is the same as this parameter.
3.4.6.12. FE37 (RX Input)
The value inputted into the RX terminal is read.
The value range is 0xD8F0 to 0x2710 (-100.00 to +100.00 %).
3.4.6.13. FE60 - FE63 (My Monitor)
Refer to the function Manual (E6581335).
3.4.6.14. FE14 (Cumulative run time)
The operated cumulative time is read by the hexadecimal number.
For example, when cumulative operation time is 18 hours, 0x12 (16 hours) is read.
0x12 (Hex.) = 18 (Dec., hour)
3.4.6.15. FE40 (Analog output (FM))
The output value of FM terminal is read.
The value range is set to 0 to 65535 (0xFFFF).
- Also about FE41 (AM terminal output monitor), it is the same as this parameter.