Toshiba T300MVI Computer Drive User Manual


 
T300MVi
T300MV i
®
4160 V MEDIUM VOLTAGE DRIVE
© 2012 Toshiba International Corporation Industrial Division 13131 West Little York Road Houston, Texas 77041 USA Tel +713-466-0277 US 1-800-231-1412 Rev. 120221
www.toshiba.com/ind
TOSHIBA INDUSTRIAL PRODUCTS:
•AdjustableSpeedDrives
•Motors
•MotorControls
•Instrumentation&PLCs
•UninterruptiblePowerSystems
MODEL RANGE
300 to 600 HP 700 to 1000 HP 1250 to 2000 HP
2250 to
2500 HP
3000 to
3500 HP
4000 to 6000 HP
7000 HP* 8000 to 10000 HP*
Voltage Rating 4160 VAC
Dimensions (H x W x D)
103.7 x 48 x 48 in. 103.7 x 60 x 48 in. 103.7 x 122 x 43.4 in.
103.7 x 164
x 49.5 in.
103.7 x 174
x 49.5 in.
103.7 x 222 x 49.5 in.
103.7 x 307.5
x 60 in.
103.7 x 402.5
x 60 in.
Weight
6,200 lbs. 7,600 lbs. 12,500 lbs. 16,500 lbs. 19,000 lbs. 27,750 lbs. 37,500 lbs. 64,800 lbs.
Current Rating (A):
37 50 62 74 87 99 112 124 155 186 217 248 279 310 372 434 496 558 620 682 744 868 992 1100 1240
Nominal HP** (4160 V)
300 400 500 600 700 800 900 1000 1250 1500 1750 2000 2250 2500 3000 3500 4000 4500 5000 5500 6000 7000 8000 9000 10000
POWER REQUIREMENTS
Input Tolerance Voltage: ±10%; Frequency: ±5%
Main Circuit Three-Phase 4160 V; Integrated 24-Pulse Copper-Wound Isolation Transformer; Five-Level NPC Medium Voltage IGBT Output
Control Circuit Integral to Main Transformer; Includes 460 V & PT for 120 V Control
Output Frequency 0 to 120 Hz
CONTROL SPECIFICATIONS INPUT
Control Method Five-Level Pulse-Width Modulation (PWM) Output Control with Neutral-Point Clamping (NPC)
V/Hz Control V/Hz, Sensorless Vector Control, Variable Torque, Closed-Loop Vector Control, & Constant Torque (Optional)
PWM Carrier Frequency Fixed at 2 kHz
Frequency Setting 4 to 20 mA, 0 to 10 VDC Serial Communication Input, & Rotary Encoder Integrated into EOI
Speed Regulation Open Loop: Up to 0.5%; Closed Loop: Up to 0.1%
Main Protective Functions Current Limit, Overcurrent, Overload, Undervoltage, Overvoltage, Ground Fault, CPU Error, & Soft Stall
Overload Current Rating 100% Continuous; 115% for One Minute Every 20 Minutes (1000, 2000, & 6000 HP at 110%)
CONTROL INTERFACE
Digital Input Eight Discrete Input Terminals with Programmable Functions
Digital Output Six Available Digital Programmable Outputs (One Used Internal to Drive)
Analog Input Two Selectable Currents (0/4 to 20 mA) or Voltage (0 to 10 VDC) Input Signals
Analog Output Eight Selectable Currents (0/4 to 20 mA) or Voltage (0 to 10 VDC) Output Signals with Programmable Function
Communication Ports Profibus, Modbus RTU, Modbus, TCP/IP, TOSLINE-S20, & DeviceNet
SAFETY FEATURES
Standard Pad-Lockable Input Fuse Disconnect Switch with Vacuum Contactor, Interlocked Doors, & Viewing Window
ELECTRONIC OPERATOR INTERFACE (EOI)
Display 6-Line x 20-Character Graphical Plain-English Back-Lit LCD Display for Programming, Monitoring, & Diagnostics
LED Indicators Run (Red)/Stop (Green) & Local (Green)
Keys Local/Remote, Enter, Mon/Prg, Esc, Run, & Stop/Reset
Monitoring
Frequency Command Screen; Multiple Parameters Displayed: Motor Current, Motor Speed, Motor Voltage, DC Voltage, Input Voltage, Output
Voltage, Run Time, Output Power, Motor kW, Motor kWH, Motor kVAH, Motor kVAR, & On-Time Control Power
CONSTRUCTION
Enclosure ANSI-61 Gray; NEMA 1 Ventilated, & IP20 Per IEC-60529; Gasket & Filter; Free-Standing; Front-Access Only
Power Cables Top/Bottom Access for Input/Motor Cables
Cooling Forced-Air Cooled (Redundant Fan Option)
Standards & Compliances NEC, NEMA, UL, ULC, ANSI, & American Recovery & Reinvestment Act Compliant
AMBIENT CONDITIONS
Ambient Temperature 0 to 40°C (50°C Option Available)
Altitude 3,281 ft. Above Sea Level (Up to 14,764 ft. Option Available)
Humidity 95% Maximum (Non-Condensing)
Installation Indoor; No Direct Sunlight; Protect from Corrosive Gases
All Information Subject to Change
*Models Not UL Listed
**Typical HP Rating of a 4-Pole Motor; Contact Factory for Applications on Constant Torque Loads