Toshiba TVS-XT120-347 Surge Protector User Manual


 
TVSS-Surge Protective Devices
*UPSTVSS061030*
UPS ADJUSTABLE SPEED DRIVES MOTORS CONTROLS INSTRUMENTATION PLC
INDUSTRIAL DIVISION
13131 West Little York Road, Houston, Texas 77041
Tel (713)466-0277 Fax (713)892-5212
US (800)231-1412 Canada (800)872-2192 Mexico 01(800)527-1204
www.toshiba.com/ind
Copyright 10/2006
Available Through:
Model Type TVS-XT140-120 TVS-XT140-277 TVS-XT120-347
Nominal Voltage Three Phase, 120/208/60 Hz
Three Phase, 277 / 480 /
60 Hz
Three Phase, 347/600/60
Hz
Maximum Continuous Operation Voltage (MCOV) 150 V 350 V 480 V
Maximum Surge Current Imax (8/20) NEMA LS1 (L-G) 140 kA 140 kA 120 kA
Let Though Voltage Level for Surge Current 10 kA (8/20) (L-G) 435 V 1025 V 1355 V
Long Duration Surge Performance
500 A Square Waveform 2msec (IEEE C62.11) 250 Hits 250 Hits 250 Hits
Response Time < 1 ns < 1 ns < 1 ns
Operating Temperature -40° to +85° C -40° to +85° C -40° to +85° C
Environmental Protection IP-65 (NEMA 4) IP-65 (NEMA 4) IP-65 (NEMA 4)
Enclosure Dimensions 12x10x6 Inches 12x10x6 Inches 12x10x6 Inches
Warranty 10 Years 10 Years 10 Years
Suitable for installation with no overcurrent protection on a circuit capable of delivering 85 kA for three (3) continuous cycles, in accordance with Section
37 of UL 1449 (High Current Abnormal Overvoltage Test).
TVSS
TVSS