DynaView Interface
15CG-SVU02B-E4
Circuit Level Mode
Top Level Mode Description
Running - Limit The compressor on the given circuit is currently running in a
limit mode.
Running - Limit Sub Modes Description
Hot Start Limit Additional stages on a given circuit are being held off based
on leaving evaporator temperature.
Condenser Pressure Limit The circuit is being inhibited from loading due to high
condenser pressure.
Low Evaporator Pressure Limit The circuit is being inhibited from loading due to low
evaporator pressure.
Circuit Level Mode
Top Level Mode Description
Preparing Shutdown The circuit is preparing to de-energize the compressor.
Preparing Shutdown Sub Modes Description
Operational Pumpdown The operational pumpdown is enabled and the circuit is
shutting down.
Circuit Level Mode
Top Level Mode Description
Shutting Down The chiller is going through the necessary steps after de-
energizing the compressor.
Shutting Down Sub Modes Description
No Circuit Sub-Modes
Circuit Level Mode
Top Level Mode Description
Misc. These sub modes may be displayed in most of the top level
circuit modes
Misc. Sub Modes Description
Defrosting The circuit is in a defrost operational mode.
Service Pumpdown The circuit is currently performing a service pumpdown.
Compressor X Running A specific compressor is running where X is A or B.
Restart Time Inhibit Cprsr X: MIN:SEC If there is accumulated Restart Inhibit Time, it must expire
before the compressor is allowed to start. X is denoted as
compressor A or B.