7
Battery Replacement Door
Under normal conditions, the original batteries in your UPS will
last several years. Battery replacement should only be performed
by qualified service personnel. Refer to “Battery Warnings” in the
Safety section on page 2. When replacing batteries, qualified
service personnel should follow this procedure: 1) turn UPS OFF;
2) remove the battery door located on the front panel; 3) pull batteries
partially out of the case; 4) make a detailed sketch of the batteries and
the polarity, color and connection of all cables; 5) disconnect battery
terminals; 6) dispose of used batteries; 7) reconnect replacement
batteries exactly as original batteries were; 8) push batteries back into
case and replace cover.*
* You may not receive full runtime until your replacement batteries have fully charged.
Specifications
Storage & Service
Storage
Turn your UPS OFF: first, engage the ON/Standby Switch and release it to place your
UPS in the “Standby” mode; then set the System Enable Switch* to “DISABLE”; finally,
disconnect the UPS power cord from the wall outlet. If you plan on storing your UPS
for an extended period of time, recharge the UPS batteries once every three months.
Follow steps #1 and #3 in the Installation section and allow the UPS to charge from
4 to 6 hours. If you leave your UPS batteries discharged for an extended period of time,
they will suffer permanent loss of capacity.
* The location of the switch varies by model. See page 3.
Service
If returning your UPS to Tripp Lite, please carefully pack the UPS using the
ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing
the symptoms of the problem. If the UPS is within the 2 year warranty period, enclose
a copy of your sales receipt.
SMART 700 RM SMART 1050 RM
Output Capacity (VA/Watts): 700/425 1050/705
Battery Runtime (Half Load/Full Load) Min.: 28/12 23/8
Battery Recharge Time: 2-4 hrs. 2-4 hrs.
Suggested Circuit: 15 amp 15 amp
Approvals: UL, cUL UL, cUL
SMART 1400 RM SMART 2200 RM
Output Capacity (VA/Watts): 1400/940 2200/1750
Battery Runtime (Half Load/Full Load) Min.: 26/10 29/13
Battery Recharge Time: 2-4 hrs. 2-4 hrs.
Suggested Circuit: 15 amp 15- or 20- amp dedicated
Approvals: UL, cUL UL, cUL
SMART 2200 RM XL SMART 3000 RM
Output Capacity (VA/Watts): 2200/1750 3000/2400
Battery Runtime (Half Load/Full Load) Min.: 29+/13+ 23+/7+
Battery Recharge Time: 2-4 hrs. 2-4 hrs.
Suggested Circuit: 20-amp dedicated 30-amp dedicated
Approvals: UL, cUL UL, cUL
ALL MODELS:
Input Voltage/Frequency (120V/60 Hz); On Line Input Voltage Range (87 - 140 Volts); Voltage-Regulated Output Voltage Range
(120V +/- 9%); On Battery Output Voltage Range (120V +/- 5%); Output Waveform Line Mode (filtered sinewave); Output Waveform Battery
Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB); AC Protection
Modes (H to N, H to G, N to G).
9811199 SmartPro Rackmount Owners Manuals.p65 6/15/99, 11:53 AM7