Tripp Lite 220/380V Power Supply User Manual


 
18
LCD Display Navigation
(continued)
“Other Information” Sub-Menu
This sub-menu allows managers to view a variety of additional UPS
System information.
UPS
Status
Code
Note: a UPS Status Code is displayed in the upper-right corner of the
screen in the following display. Use the chart below to determine what
the UPS Status Code indicates.
Displayed UPS Status
0 Bypass Output Inhibited
2 Load on Reserve
10 Rectifier AC Soft-Start
18 Performing Inverter Test
20 Load on Inverter
22 Load on Inverter at Backup Mode
24 Low Battery
26 Low Battery Shutdown
28 Short-Circuit Shutdown
30, 58 Manual Bypass On
32 Parallel Communication Cable Abnormal
34 Inverter Fault Shutdown
36 Inverter Overload Shutdown
38 Overload Under Parallel (N-1)
40, 42 Inverter Output Voltage Abnormal
44 Inverter IGBT Driver Protection
(Output Voltage Abnormal)
46 EPO Event Shutdown
50 DC BUS Overvoltage Protection Shutdown
52, 54, 56 Inverter Fuse Open (R/S/T Phase)
60, 62, 64 Inverter Over-temperature Shutdown (R/S/T Phase)
66 Output Transformer Over-temperature Shutdown
68, 70 Auxiliary Power Abnormal (PCB-C/A)
72 Feedback Protection
LCD Navigation Key
Action Buttons to Push
Scroll Up Through Menu
Scroll Down Through Menu
Enter or Select a Menu Choice
Exit Current Menu and Return to Previous Menu and simultaneously
Code